SV800/SV800A User Manual 3 Mechanical Installation
21
Table 3-3 Installation clearance requirements
for each power class of the SV800
Fig. 3-2 Installation clearance of multiple inverters
Different rows installation
If one row of inverters need to be installed above another row, please install insulation guide
plate to prevent the heat from the lower row inverters which will cause the temperature of the
upper row inverters to raise, even over-heat and overload fault occurs. Measures as shown in
Fig.3-3
:
Fig.3-3 Up and down row installation requirements
Power level
Space requirement
(mm)
2.2KW~22KW
A≥10
30~37KW
A≥50
≥45KW
A≥50
A