SV800/SV800A User Manual 7 Detailed function description
191
During water shortage alarm, it outputs ON signal. It becomes OFF after the fault recovery.
38-39: Reserved
40: Brake control output
When the brake control signal is valid, it outputs ON signal.
No.
Name
Set range
Factory default
H1-05
Multi-function relay output M1 delay time
0.0s
~
3600.0s
0.0s
H1-06
Multi-function relay output M2 delay time
0.0s
~
3600.0s
0.0s
When delay time set in H1-05 and H1-06,the relay M1 and M2 will output ON signal after the
delay time when the signal is valid.
Fig.7-28 Delay output
No.
Name
Set range
Factory default
H1-07
Detection speed 1
0.0%
~
100.0%
0.0%
H1-08
Detection speed 2
-100.0%
~
100.0%
0.0%
Used to set the detection speed level, which is percentage value of
E0-02
.
No.
Name
Set range
Factory default
H1-09
Speed detection amplitude
0.0%
~
40.0%
0.0%
The amplitude used with multi-function DO “Speed arrives ” together, it’s percentage value of
E0-02
.
No.
Name
Set range
Factory default
H1-10
Torque detection instruction (Bipolarity)
-305%
~
305%
0%
H1-11
Torque Detection Instruction (Absolute
Value)
0%
~
305 %
0%
H1-10
and
H1-11
used to set the torque detection level, which used with multi-function DO
"Torque detection" and "Absolute torque detection" together. The DO outputs ON signal when
Set speed
Time
ON
ON
Speed arrival
ON
Speed arrival
ON
H1-05/
H1-06
Output speed
Detection
amplitude
H1-05/
H1-06