SV800/SV800A User Manual 8 Fault and maintenance
211
LCD keyboard
display
LED keyboard
display
Fault Name
Communication
code
FCLoL
FCLoL
FCL overload fault
24
Possible causes
Countermeasures
Acc./Dec. time too short (V/F control)
Increase Acc./Dec. time
The load too heavy
Reduce the load or replace drive and motor with larger power
Fast current limiting threshold setting
abnormal
Reset the fast current limiting threshold (visible when
allowed by manufacturer)
Improper selection of inverter or motor
Reduce the load or reselect the inverter and motor
Continuous heavy load operation at low
frequency(<5.0Hz)
Select inverter with larger power and re-rate using
Fast current limit signal abnormal
Replace the control board
LCD keyboard
display
LED keyboard
display
Fault Name
Communication
code
SEr
5Er
Speed tracking fault
25
Possible causes
Countermeasures
Motor
nameplate
parameters
setting
abnormal
Correctly set the motor nameplate parameters
Self-learning parameter input abnormal
Input motor parameters correctly and perform full mode
self-learning
Abnormal voltage detection signal
Check if the inverter voltage detection is correct or replace
the control board when cannot confirm.
Abnormal current detection signal
Check if the inverter current detection is correct or replace
the control board when cannot confirm.
LCD keyboard
display
LED keyboard
display
Fault Name
Communication
code
PtA
PtA
Power-on time arrives
27
Possible causes
Countermeasures
Inverter power-on time arrives
Contact manufacturer or supplier
LCD keyboard
display
LED keyboard
display
Fault Name
Communication
code
rtA
rtA
Run time arrives
28
Possible causes
Countermeasures
Run time arrives
Contact manufacturer or supplier
LCD keyboard
display
LED keyboard
display
Fault Name
Communication
code
CoEr
CoEr
Communication timeout fault
29