SV800/SV800A User Manual 7 Detailed function description
147
b2-12
Second motor inductance saturation compensation
coefficient 1
Determined with the
model
Change with the model
(0.0%)
b2-13
Second motor inductance saturation compensation
coefficient 2
Determined with the
model
Change with the model
(0.0%)
b2-14
Second motor iron loss conductance
0.0mho
~
600.0mho
Change with the model
(0.0mho)
b2-15
Second motor loss factor 1
0.0%
~
200.0%
Change with the model
(0.0%)
b2-16
Second motor loss factor 2
0.0%
~
200.0%
Change with the model
(0.0%)
The set of parameters is the motor electrical constant necessary for vector control operations.
For the details, please refer to the first motor parameter description.
7.3 d: debugging and controlling parameters
Through group d parameters, you can set the speed control, command input selection, speed
loop auxiliary function module, torque control, V/F control. All debugging or control
parameters related to speed and torque control in the motor control algorithm are classified in
this group of parameters.
7.3.1 d0: speed control debugging parameters
This group of parameters mainly sets the parameters of the speed loop regulator in the speed
control. The first motor and the second motor can be set separately. It also includes the selection
and debugging of the speed observer, torque observer, variable structure control functions,
selection and setting of spare speed loop proportional factor.
No.
Name
Set range
Factory default
d0-00
First motor speed control proportional gain
3
~
100
15
d0-01
First motor speed control integral time constant
20ms
~
10000ms
40 ms
d0-02
First motor speed control rotation inertia
0 gm²
~
65535 gm²
10 gm²
Set d0-00 to set the proportional gain of the first motor speed loop regulator.
Set d0-01 to set the integration time constant of the first motor speed loop regulator, also
corresponds to the integral gain
Set d0-02 to set the rotational inertia of the first motor speed control. When setting the rotation
inertia, it is set in the unit of gm2. For details, please refer to
"
5.6.2 Setting of Motor rotation
inertia
" and "
5.6.3 Setting of Speed Control Proportional Coefficient and Integration Time
Constant
"
No.
Name
Set range
Factory default
d0-03
Second motor speed control proportional gain
3
~
100
15
d0-04
Second motor speed control integral time constant
20ms
~
10000ms
40 ms
d0-05
Second motor speed control moment of inertia
0 gm²
~
65535 gm²
10 gm²
The usage is the same as the first motor. For details, refer to "
5.6.2 Setting of Motor rotation
inertia
" and "
5.6.3 Setting of Speed Control Proportional Coefficient and Integration Time
Constant
".