7 Detailed function description SV800/SV800A User Manual
192
the detected torque reaches the set value.
No.
Name
Set range
Factory default
H1-12
Overload pre-alarm setting
0%
~
100%
50%
It used with multi-function DO “
Overload pre-alarm setting
” together.
H1-12
is a percentage
value of the motor rated current.
No.
Name
Set range
Factory default
H1-13
TA-TB-TC Relay Function Selection
0
~
40
17
The Factory default is defined as inverter fault. Other functions as same as
H1-00
.
7.6.3 H2: Multi-function Analog input AI
No.
Name
Set range
Factory default
H2-00
Analog input AI1 range selection
0
~
2
0
0:0~10V
The negative input signal is limited to 0V.
1:Reserved
2:4~20mA
Please put the S2 dip
switch
on the right position when select voltage or current signal in
H2-00
.
Factory default is voltage signal.
No.
Name
Set range
Factory default
H2-01
AI1 gain setting
-300.0%
~
300.0%
100.0%
H2-02
AI1 bias setting
-300.0%
~
300.0%
0.0%
Please refer to
Fig.7-29
for gain and bias settings:
Fig. 7-29 AI input
x
0V/0mA
10V/20mA
0V/0mA
y
Gain:125.0%
,
bias:-25.0%
100%
-25%
x
100%
10V/20mA
y
Gain:100.0%
,
bias:0.0%