![SCOV SV800 Series User Manual Download Page 202](http://html.mh-extra.com/html/scov/sv800-series/sv800-series_user-manual_1219567202.webp)
7 Detailed function description SV800/SV800A User Manual
194
7.6.4 H3: Multi-function analog output AO
No.
Name
Set range
Factory default
H3-00
Multi-function AO1 function selection
0
~
12
3
Please refer to information in Table 7 -5 for specific settings.
No.
Name
Set range
Factory default
H3-01
Multi-function AO1 range selection
0
~
2
0
0:0~10V
1:Reserved
2:4~20mA
The gain and bias of AO1 set in
H3-02
and
H3-03
.
Please put S1 DIP switch on the right
position
when voltage or current signal selected in
H3-01
.
No.
Name
Set range
Factory default
H3-02
AO1 gain setting
-300.0%
~
300.0%
100.0%
H3-03
AO1 bias setting
0.0%
~
300.0%
0.0%
For the setting method, please refer to
Fig. 7-30
:
Fig. 7-30 AO analog output
Xmax: The required Max. output of AO.
No.
Name
Set range
Factory default
H3-04
AO1 filter time
0.00s
~
10.00s
0.10s
H3-05
Multi-function AO2 function selection
0
~
12
0
Please refer to information in Table 7 -5 for specific settings.
No.
Name
Set range
Factory default
H3-07
AO2 gain setting
-300.0%
~
300.0%
100.0%
H3-08
AO2 bias Setting
0.0%
~
300.0%
0.0%
Gain:80.0%
,
bias:20.0%
x
x
Xmax
Xmax
10V/20mA
10V/20mA
y
y
0V/0mA
0V/0mA
2V/4mA
Gain:100.0%
,
bias:0.0%