7 Detailed function description SV800/SV800A User Manual
188
The status of DI is valid when
the
DI not connect to COM.
Bit0-bit 5 relating to DI~DI6.
No.
Name
Set range
Factory default
H0-13
Multi-function input terminals filtering time 1
0.000s
~
1.000s
0.010s
H0-14
Multi-function input terminals filter time 2
0.000s
~
1.000s
0.010s
H0-13
and
H0-14
are the filter time for DI1~DI12 terminals,
H0-13
for DI1 and DI2,
H0-14
for
DI3~DI6. The anti-interference ability of the terminal can be effectively improved by setting
proper filter time, but too large value will lead to slow response of DI.
No.
Name
Set range
Factory default
H0-15
Terminal Start/Stop control mode
0
~
3
0
0: Two-wire mode 1
1: Two-wire mode 2
2: Three-wire mode 1
3: Three-wire mode 2
For more details, please refer to the function “3-wire operation control ” with function code 5 in
multi-function terminal.
7.6.2 H1: Multi-function output terminals
No.
Name
Set range
Factory default
H1-00
Multi-function output terminal DO1
0
~
40
0
H1-01
Multi-function output terminal DO2
0
~
40
0
H1-03
Multi-function output terminal M1
0
~
40
35
H1-04
Multi-function output terminal M2
0
~
40
0
0: No function
1: End of Simple PLC multi-step operation
When one cycle of simple PLC completed, it outputs ON signal and lasts 500 ms.
2: Detection speed 1 (Detection speed =
speed in H1-07
)
When the output speed = the speed set in H1-07, it outputs ON signal.
3: Speed detection 1 (Detection speed ≥speed in H1-07)
When the output speed
≥
the speed set in H1-07, it outputs ON signal.
4: Speed detection 1 (Detection speed ≤speed in H1-07)
When the output speed
≤
the speed set in H1-07, it outputs ON signal.
5: Speed detection 2 (Detection speed =
speed in H1-08
)
When the output speed = the speed set in H1-07, it outputs ON signal.
6: Speed detection 2 (Detection speed ≥speed in H1-08)
When the output speed
≥
the speed set in H1-07, it outputs ON signal.