SV800/SV800A User Manual 6 Function Parameters List
115
F0: PID control parameters
No.
Name
Content
Set value
F0-19
(5013H)
PID initial value hold
time
ALL
Factory default
:
0.00s
Range
:
0.00s~600.00s
F0-20
(5014H)
PID parameter switching
condition
ALL
0: Not switch
1: Switch by DI terminal
2: Automatic switching according to deviation
3: Reserved
Factory default
:
0
Range
:
0~3
F0-21
(5015H)
PID parameter switching
deviation 1
ALL
Factory default
:
20.00%
Range
:
0.00%~[F0-22]
F0-22
(5016H)
PID parameter switching
deviation 2
ALL
Factory default
:
80.00%
Range
:
[F0-21]~100.00%
F0-23
(5017H)
Forward Max. of two
output deviations
ALL
Factory default
:
1.00%
Range
:
0.00%~100.00%
F0-24
(5018H)
Reverse Max. of two
output deviations
ALL
Factory default
:
1.00%
Range
:
0.00%~100.00%
F0-25
(5019H)
PID integral attribute
ALL
Units digits:
Integral separated
0: Invalid
1: Valid
Tens digits:
Stop the integration when the output reaches the
limit
0: Continue
1: Stop
Factory default
:
0x00
Range
:
0x00~0x11
F0-26
(501AH)
PID feedback
disconnection detection
threshold
ALL
0.0%
~
100.0
%
0.0%
:
Means not detection
Factory default
:
0.0%
Range
:
0.0%~100.0%
F0-27
(501BH)
PID feedback
disconnection detection
time
ALL
Factory default
:
0.0S
Range
:
0.0S~20.0S
F0-28
(501CH)
PID Calculating at Stop
state
ALL
0:Invalid
1: Valid
Factory default
:
0
Range
:
0~1
F0-29
(501DH)
PID upper limit
frequency
ALL
Factory default
:
50.00Hz
Range
:
F0-30~E0-02
Summary of Contents for SV800 Series
Page 8: ......