SV800/SV800A User Manual 7 Detailed function description
169
0: Normal mode
Restart from the current given frequency which between the upper or low limit. If it exceeds the
range, running at the limit frequency.
1: Save when Stop
Save the speed/frequency when the inverter stops. Restart from the saved speed/frequency.
2: Save when Power off
Save the speed/frequency when under-voltage fault occurs. Restart from the saved
speed/frequency.
E3-07
and
E3-08
a
re the upper lim
it and low limit frequency for UP/ DOWN function. When
negative value set in
E3-08
, forward and reverse operation can be switched by UP/ DOWN
command.
No.
Name
Set range
Factory default
E3-09
Speed deviation limit function selection
0
~
1
0
E3-10
Positive deviation speed
0.0%
~
100.0%
5.0%
E3-11
Negative deviation speed
-100.0%
~
0.0%
-5.0%
0:OFF
1:ON
The function is used when the transmission mechanism does not allow the speed changes
steeply. It used to set the speed deviation limit during acceleration or deceleration, just valid for
vector control. The value in E3-10 and E3-11 are percentage value that relating to E0-00.
Note: When the speed deviation limit function is selected, d2-11 should be set as 0. Because the output torque
is limited and processed when the anti-reverse function is enabled.
7.4.5 E4:Simple PLC and multi-speed
No.
Name
Set range
Factory default
E4-00
Simple PLC operation mode
0
~
3
0
0: OFF
1: Stop after single cycle
The inverter stop automatically after perform one cycle.