SV800/SV800A User Manual Appendix D: A1 application selection and parameter mapping
235
No.
Name
Factory default
Description
Mapping
parameter
A1-20
Wake up pressure
0.00MPa
set to sleep slower, wake up
faster, wake up pressure is less
than target pressure
F1-05
A1-21
Wake delay time
0.0s
F1-06
A1-22
DO1 function
0: No function
31: Connect 1# pump to
inverter
H1-00
A1-23
DO2
function
selection
0: No function
32: Connect 1# pump to power
supply
H1-01
A1-24
M1 Relay function
35: Running (including DC
braking)
33: Connect 2# pump to
inverter
H1-03
A1-25
M2 Relay function
0: No function
34: Connect 2# pump to power
supply <1>
H1-04
A1-26
Upper
limit
frequency
50.00Hz
Set according to requirements
E0-00
A1-27
Low
limit
frequency
0.00Hz
E0-01
A1-28
Max. frequency
50.00Hz
E0-02
A1-29
PID
Proportional
Gain KP1
20.0
F0-06
A1-30
PID
integration
time TI1
2.00S
F0-07
A1-31
Prohibit Reversal
Mode Selection
0: OFF
2: Prohibit reverse running
d2-11
A1-32
DI4 function
20: Fault reset
Refer to Chapter 7 for details
H0-03
A1-33
TA-TB-TC relay
17: Inverter failure
Refer to Chapter 7 for details
H1-13
A1-34
AO1 function
3:
Inverter
output
frequency
Refer to Chapter 7 for details
H3-00
A1-35
Motor
overload
protection setting
100%
P0-03
A1-36~
A1-49
Retain
<1> When the F1-00=2 (One inverter two Pumps), the inverter will add or remove the pumps automatically
by four digital output control signals DO1, DO2, M1 and M2.