Appendix D: A1 application selection and parameter mapping SV800/SV800A User Manual
232
D.2 Application of air supply/exhaust fan (A1-00=2)
No.
Name
Factory default
Description
Mapping
parameter
A1-01
Control mode setting
2: V/F control
V/F control for generally
using
A0-04
A1-02
G/P model selection
0: G type
1:P type
A0-12
A1-03
Run command input
selection
0: Keyboard control
1: Terminal control
2: Communication control
d1-00
A1-04
Main
frequency
command
input
selection
0: Keyboard parameter
(E1-00)
setting
(keyboard potentiometer
valid)
1:
Keyboard
parameter
(E1-00) setting (keyboard
potentiometer is invalid)
2: AI1
3~9: Refer to the detailed
description
d1-01
A1-05
Frequency 1
50.00Hz
E1-00
A1-06
Acc. time 1
Determined
with
the
model
Set
according
to
requirements
E2-02
A1-07
Dec. time 1
Determined
with
the
model
Set
according
to
requirements
E2-03
A1-08
DI1 function .
3: Forward running
Refer to Chapter 7 for
details.
H0-00
A1-09
M1 relay function
35: Running (including
DC braking)
Refer to Chapter 7 for
details.
H1-03
A1-10
TA-TB-TC
relay
function
17: Inverter failure
Refer to Chapter 7 for
details.
H1-13
A1-11
Upper limit frequency
50.00Hz
Set
according
to
requirements
E0-00
A1-12
Low limit frequency
0.00Hz
E0-01
A1-13
Max. frequency
50.00Hz
E0-02
A1-14
Start mode selection
1:
Start
from
Min.
frequency (E0-03)
Generally set to 0: Start by
speed tracking
d4-04
A1-15
Stop mode selection
1: deceleration stop
0: Free stop
d2-06
A1-16
Anti-Regeneration stall
function Selection
0:OFF
Generally set to 1: ON
d2-13
A1-17
Torque boost
Determined
with
the
model
Generally set to 0%
d4-01
A1-18
Prohibit
Reversal
Mode Selection
0: OFF
2: Prohibit reverse running
d2-11
A1-19
DI4 function
20: Fault reset
Refer to Chapter 7 for
details.
H0-03
A1-20
AI1 input signal type
0:0~10V
1:4~20mA
(S2
switch
needs to be switched to
current side)
H2-00