B.1.5 Register address of control parameters
Register address
Parameter Name
Remarks
0x6000
Control command word
0x6001
Main speed/frequency
0x6002
Auxiliary speed/frequency
0x6003
PID communication given
0x6004
PID communication feedback
0x6005
Torque communication setting
0x6006
Torque compensation
communication setting
0x6007
Motoring torque
0x6008
Braking torque
0x6009
Speed positive side limit
0x600A
Speed negative side limit
0x600B
DO terminal communication
given
The control command words definition is as follows
Control command
word 0x6000
Value
Meaning
Function description
bit0
0
Running commands
invalid
Invalid
1
Running commands
valid
Start inverter
bit1
0
Forward
Direction setting
1
Reverse
bit2
0
Invalid
1
Jog run
bit3
0
Invalid
1
Reset command valid
bit4
0
Invalid
1
Dec. Stop valid
bit5
0
Invalid
1
Stop freely valid
bit6~bit15
Reserved