3.5
Date Code 20120126
Instruction Manual
SEL-2032 Communications Processor
Job Done Examples
Example 2: Using the SEL-2032 as a Port Switch
Step 2. Connect the IRIG-B time source to the SEL-2032 IRIG-B
input. (You need to know if the time source has a modulated or
demodulated IRIG-B signal. Set IRIG setting accordingly.)
NOTE
: You do not need to modify the
baud rate of Port 2 at the relay; the
SEL-2032 will match the baud rate
during auto-configuration.
Step 3. Connect the modem to Port 9 using cable SEL-C226,
and
connect a telephone line to the phone line connector on the
modem.
Step 4. Connect the serial port on your computer to Port F on the
SEL-2032 with an SEL C234A cable.
Set the SEL-2032
Step 1. Issue the
ACCESS
and
2ACCESS
commands and associated
passwords to go to Access Level 2.
Step 2. Use
SET P F
to set Port F parameters.
Step 3. Set Port 1 configuration communications options using the
SET P 1
command.
Step 4. Use
SET A 1
to define a timed trigger condition in the form of
(Thh:mm:ss) to send a date message at a specific time once
each day to the relay connected to Port 1.
Step 5. Use the
COPY 1 ALL
command to copy Port 1 settings to the
other ports (2, 3, 4, 5, 6, and 7) with devices attached.
Step 6. Use
SET P 9
to set Port 9 as a modem port.
Verify and Test All Communication Paths
Step 1. Use the
STATUS
command to check that the IRIG-B signal is
present and devices are connected to ports as expected.
Step 2. Check transparent communication with each port.
➢
Use the
PORT
n
command to enter transparent
communication with Port
n
, where
n
is any port number
(1–16).
➢
Use
<Ctrl+D>
to end transparent communication.
Step 3. Check that all SEL relays are receiving the proper IRIG-B
signal from the SEL-2032, that all relays have their Port 2 set to
issue auto-messages, and that the relay Port 2 time-out is OFF.
➢
Enter Transparent Communication with each port,
Access Level 1, and issue the
IRIG
command.
➢
Issue the
SHO
command to check the relay’s AUTO
and TIME settings.
➢
Exit transparent communication using the default
disconnect sequence,
<Ctrl+D>
.
Step 4. Check that the SEL-2032 issues the correct date code to each
relay. Change the relay date to the wrong year; use the
TOGGLE
command to issue the SEL-2032 date message.
Step 5. Check modem communication.
➢
Have someone call; the SEL-2032 modem should
answer by the fourth ring.
➢
The remote caller can enter transparent communication,
and you can watch the communication using front-
panel LEDs and the
STATUS
command.
Summary of Contents for SEL-2032
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...