7.37
Date Code 20120126
Instruction Manual
SEL-2032 Communications Processor
Settings
Global (SET G) Settings
Global settings include primarily the intermediate logic and optional output
contact logic available in the SEL-2032.
lists all Global settings
and their description strings. You should use
SET G
to modify and
SHO G
to
view these settings.
Each of the five intermediate logic variables (V, W, X, Y, and Z) described in
has corresponding generic pickup/dropout timers. For the output of
a timer to be asserted, its input must first be asserted for the pickup time. Once
a timer is asserted, for its output to be deasserted, its input must be deasserted
for the dropout time. If an I/O board is installed, you may define conditions
that assert outputs on the board.
You define the logic elements using SEL
OGIC
control equations and set their
timers using the
SET G
command. For a complete discussion of these
equations, see
.
includes a complete description of the
SET G
settings.
Table 7.11
Global (SET G) Settings and Definitions
(Sheet 1 of 2)
Setting
Comment
Description
ID
Device Identification.
Any string of up to 40 characters that you wish to use to identify
this device.
TIME_SRC
SEL-2032 Time Synchronization source
(IRIG, DNP, OFF, PC1, PC2).
Select the source used by the SEL-2032 to time-synchronize
itself.
IRIG_SIG
Type of IRIG Source (Modulated/Demodulated)
Use this setting to select the type of IRIG-B input you are
expecting. If you are using the port 15 IRIG-B input, this setting
must be demodulated. If you are not using any IRIG-B input,
we recommend that you set it to demodulated.
PCFAIL
PCFAIL= Enter
a
SEL
OGIC
control equation to control the PCFAIL global
status element. The default equation causes the PCFAIL bit to
assert if a card is present, but not alive and initialized.
LOG_EN
Enable use of intermediate logic (Y/N).
There are five intermediate logic variables, three of which have
associated timers. You set this setting to Y (Yes) to enable their
use, or set it to N (No) if you do not plan to use them.
V
V=
You enter a SEL
OGIC
control equation definition
for the intermediate logic element V.
W
W=
You enter a SEL
OGIC
control equation definition
for the intermediate logic element W.
X
X=
You enter a SEL
OGIC
control equation definition for the
intermediate logic element X.
Y
Y=
You enter a SEL
OGIC
control equation definition for the
intermediate logic element Y.
Z
Z=
You enter a SEL
OGIC
control equation definition
for the intermediate logic element Z.
VPICKUP
V Timer Pickup time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
VDROPOUT
V Timer Dropout time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
WPICKUP
W Timer Pickup time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
WDROPOUT
W Timer Dropout time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
XPICKUP
X Timer Pickup time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
XDROPOUT
X Timer Dropout time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
YPICKUP
Y Timer Pickup time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
YDROPOUT
Y Timer Dropout time (seconds).
The range is 0.0–86400.0 seconds in 0.1-second increments.
Summary of Contents for SEL-2032
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...