D.12
SEL-787 Relay
Instruction Manual
Date Code 20081022
DNP3 Communications
DNP3 in the SEL-787
The modem settings in
are only available for DNP3 serial port
sessions.
Configurable Data
Mapping
One of the most powerful features of the SEL-787 implementation is the
ability to remap DNP3 data and, for analog values, specify per-point scaling
and dead bands. Remapping is the process of selecting data from the reference
map and organizing it into a data subset optimized for your application. The
SEL-787 uses object and point labels, rather than point indices, to streamline
the remapping process. This enables you to quickly create a custom map
without having to search for each point index in a large reference map.
You may use any of the three available DNP3 maps simultaneously with up to
three unique DNP3 masters. Each map is initially populated with default data
points, as described in
. You may remap the
points in a default map to create a custom map with up to:
➤
100 Binary Inputs
➤
32 Binary Outputs
➤
100 Analog Inputs
➤
32 Analog Outputs
➤
32 Counters
You can use the
SHOW DNP
x
<Enter>
command to view the DNP3 data
map settings, where
x
is the DNP3 map number from 1 to 3. See
for an example display of map 1.
Table D.8
Serial Port DNP3 Modem Settings
Name
Description
Range
Default
MODEM
Modem connected to port; all following
settings are hidden if MODEM set to N
Y, N
N
MSTR
Modem startup string
Up to 30
characters
"E0X0&
D0S0=4"
PH_NUM1
Primary phone number for dial-out
Up to 30
characters
“”
PH_NUM2
Secondary phone number for dial-out
Up to 30
characters
“”
RETRY1
Retry attempts for primary dial-out; hidden and
unused if PH_NUM2 set to “”
1–20
5
RETRY2
Retry attempts for secondary dial-out; hidden
and unused if PH_NUM2 set to “”
1–20
5
MDTIME
Time from initiating call to failure due to no
connection, seconds
5–300
60
MDRET
Time between dial-out attempts
5–3600
120
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...