Instruction Manual
SEL-787 Relay
SET.9
of 68
SEL-787 Settings Sheets
Group Settings (SET Command)
RTD10 LOCATION (OFF, AMB, OTH)
RTD10LOC :=
RTD10 IDENTIFIER (10 characters)
(Hidden if RTD10LOC := OFF or AMB)
RTD10NAM:=
RTD10 TYPE (PT100, NI100, NI120, CU10)
(Hidden if RTD10LOC := OFF)
RTD10TY
:=
RTD10 TRIP LEVEL (OFF, 1–250 degC)
(Hidden if RTD10LOC := OFF)
TRTMP10 :=
RTD10 WARN LEVEL (OFF, 1–250 degC)
(Hidden if RTD10LOC := OFF)
ALTMP10 :=
RTD11 LOCATION (OFF, AMB, OTH)
(Hidden if E49RTD := INT)
RTD11LOC :=
RTD11 IDENTIFIER (10 characters)
(Hidden if RTD11LOC := OFF or AMB, or E49RTD := INT)
RTD11NAM:=
RTD11 TYPE (PT100, NI100, NI120, CU10)
(Hidden if RTD11LOC := OFF or E49RTD := INT)
RTD11TY
:=
RTD11 TRIP LEVEL (OFF, 1–250 degC)
(Hidden if RTD11LOC := OFF or E49RTD := INT)
TRTMP11 :=
RTD11 WARN LEVEL (OFF, 1–250 degC)
(Hidden if RTD11LOC := OFF or E49RTD := INT)
ALTMP11 :=
RTD12 LOCATION (OFF, AMB, OTH)
(Hidden if E49RTD := INT)
RTD12LOC :=
RTD12 IDENTIFIER (10 characters)
(Hidden if RTD12LOC := OFF or AMB, or E49RTD := INT)
RTD12NAM:=
RTD12 TYPE (PT100, NI100, NI120, CU10)
(Hidden if RTD12LOC := OFF or E49RTD := INT)
RTD12TY
:=
RTD12 TRIP LEVEL (OFF, 1–250 degC)
(Hidden if RTD12LOC := OFF or E49RTD := INT)
TRTMP12 :=
RTD12 WARN LEVEL (OFF, 1–250 degC)
(Hidden if RTD12LOC := OFF or E49RTD := INT)
ALTMP12 :=
Phase Undervoltage
(Hidden if voltages not included.)
PHASE UV LEVEL (OFF, 12.5–300.0 V)
27P1P
:=
PHASE UV DELAY (0.0–120.0 sec)
(Hidden if 27P1P := OFF)
27P1D
:=
PHASE UV LEVEL (OFF, 12.5–300.0 V)
27P2P
:=
PHASE UV DELAY (0.0–120.0 sec)
(Hidden if 27P2P := OFF)
27P2D
:=
Phase Overvoltage
(Hidden if voltages not included.)
PHASE OV LEVEL (OFF, 12.5–300.0 V)
59P1P
:=
PHASE OV DELAY (0.0–120.0 sec)
(Hidden if 59P1P := OFF)
59P1D
:=
PHASE OV LEVEL (OFF, 12.5–300.0 V)
59P2P
:=
PHASE OV DELAY (0.0–120.0 sec)
(Hidden if 59P2P := OFF)
59P2D
:=
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...