6.4
SEL-787 Relay
Instruction Manual
Date Code 20081022
Settings
View/Change Settings Over Communications Port
View/Change Settings Over Communications Port
Refer to
for information on how to set up and
access the relay serial or Ethernet port with a personal computer and how to
use ASCII commands to communicate with the relay.
View Settings
Use the
SHOW
command to view relay settings. The
SHOW
command is
available from Access Level 1 and Access Level 2.
lists the
SHOW
command options.
You may append a setting name to each of the commands to specify the first
setting to display (e.g.,
SHO 50P11P
displays the relay settings starting with
setting
50P11P
). The default is the first setting. The
SHOW
command
displays only the enabled settings.
Enter Settings
The
SET
command (available from Access Level 2) allows you to view or
lists the
SET
command options.
You may append a setting name to each of the commands to specify the first
setting to display (e.g.,
SET 50P1P
displays the relay settings starting with
setting 50P1P). The default is the first setting.
When you issue the
SET
command, the relay presents a list of settings one at
a time. Enter a new setting or press
<Enter>
to accept the existing setting.
Editing keystrokes are listed in
.
Table 6.2
SHOW Command Options
Command
Description
SHOW
Show relay group settings.
SHO D
Show DNP3 map settings.
SHO F
Show front-panel display and LED settings.
SHO G
Show global configuration settings.
SHO L
Show logic settings.
SHO M
Show Modbus map settings.
SHO P
n
Show serial port settings for Port
n
(
n
= F, 1, 2, 3, or 4).
SHO R
Show Sequential Event Report (SER) and Event Report settings.
Table 6.3
SET Command Options
Command
Settings Type
Description
SET
Relay
Protection elements, timers, etc.
SET D
DNP
DNP3 map settings
SET F
Front Panel
Front-panel display and LED settings
SET G
Relay
Global configuration
SET L
Logic
General logic settings
SET M
Modbus
Modbus user map
SET P
Port
Serial port settings
SET R
Reports
SER and Event Report settings
NOTE:
The
SET
command is not
available up to 90 seconds after the
relay is powered up and up to
40 seconds after a setting change. If
you issue a
SET
command during this
period, the relay responds with the
following message:
Command Unavailable;
Relay Configuration in
Progress, Try Again.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...