Date _______________
Group______________
Date Code 20081022
Instruction Manual
SEL-787 Relay
SET.3
of 68
SEL-787 Settings Sheets
Group Settings (SET Command)
PHASE IOC DELAY (0.00–5.00 sec)
(Hidden if 50P13P := OFF)
50P13D
:=
PH IOC TRQCTRL (SEL
OGIC
)
(Hidden if 50P13P := OFF)
50P13TC
:=
PHASE IOC LEVEL (OFF, 0.50–96.00 A [5 A nom.],
0.10–19.20 A [1 A nom.])
50P14P
:=
PHASE IOC DELAY (0.00–5.00 sec)
(Hidden if 50P14P := OFF)
50P14D
:=
PH IOC TRQCTRL (SEL
OGIC
)
(Hidden if 50P14P := OFF)
50P14TC
:=
Winding 1 Residual Overcurrent
(All settings below are hidden when W1CT := DELTA.)
RES IOC LEVEL (OFF, 0.50–96.00 A [5 A nom.],
0.10–19.20 A [1 A nom.])
50G11P
:=
RES IOC DELAY (0.00–5.00 sec)
(Hidden if 50G11P := OFF)
50G11D
:=
RES IOC TRQCTRL (SEL
OGIC
)
(Hidden if 50G11P := OFF)
50G11TC
:=
RES IOC LEVEL (OFF, 0.50–96.00 A [5 A nom.],
0.10–19.20 A [1 A nom.])
50G12P
:=
RES IOC DELAY (0.00–5.00 sec)
(Hidden if 50G12P := OFF)
50G12D
:=
RES IOC TRQCTRL (SEL
OGIC
)
(Hidden if 50G12P := OFF)
50G12TC
:=
Winding 1 Negative-Sequence Overcurrent
NSEQ IOC LEVEL (OFF, 0.50–96.00 A [5 A nom.], 0.10–
19.20 A [1 A nom.])
50Q11P
:=
NSEQ IOC DELAY (0.00–5.00 sec)
(Hidden if 50Q11P := OFF)
50Q11D
:=
NSEQ IOC TRQCTRL (SEL
OGIC
)
(Hidden if 50Q11P := OFF)
50Q11TC
:=
NSEQ IOC LEVEL (OFF, 0.50–96.00 A [5 A nom.],
0.10–19.20 A [1 A nom.])
50Q12P
:=
NSEQ IOC DELAY (0.00–5.00 sec)
(Hidden if 50Q12P := OFF)
50Q12D
:=
NSEQ IOC TRQCTRL (SEL
OGIC
)
(Hidden if 50Q12P := OFF)
50Q12TC
:=
Winding 1 Maximum Phase Time Overcurrent
PHASE TOC LEVEL (OFF, 0.50–16.00 A [5 A nom.],
0.10–3.20 A [1 A nom.])
51P1P
:=
PHASE TOC CURVE (U1, U2, U3, U4, U5, C1, C2, C3, C4,
C5)
(Hidden if 51P1P := OFF)
51P1C
:=
PHASE TOC TDIAL (0.50–15.00 for U1–U5 OR 0.05–1.00 for
C1–C5)
(Hidden if 51P1P := OFF)
51P1TD
:=
EM RESET DELAY (Y, N)
(Hidden if 51P1P := OFF)
51P1RS
:=
CONST TIME ADDER (0.00–1.00 sec)
(Hidden if 51P1P := OFF)
51P1CT
:=
MIN RESPONSE TIM (0.00–1.00 sec)
(Hidden if 51P1P := OFF)
51P1MR
:=
PH TOC TRQCTRL (SEL
OGIC
)
(Hidden if 51P1P := OFF)
51P1TC
:=
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...