5.17
Date Code 20081022
Instruction Manual
SEL-787 Relay
Metering and Monitoring
Through-Fault Event Monitoring
IA, IB, and IC show the maximum primary current for each phase, with a
maximum of 100,000 A primary.
A, B, and C show the amount (percent increase) of the present fault for each
phase. Alarm shows those phase(s) that were in the alarm state at the end of
the through-fault event.
shows events report messages and the reason why these messages
may appear in the events report.
Use the
TFE A
command to list all the stored through-fault events (not only
the last 20 events) since the monitor was last reset. To list a particular number
of through-fault events, enter the
TFE
n
command (
n
= 1 to 500).
To clear event accumulated data, and all event records, use either the
TFE C
(clear) or
TFE R
(reset) command. Both commands have the same result, so
you can use either of them. Note that when you change the ETHRFLT setting,
the relay also clears the data and records, i.e. it has the same effect as the
TFE C
or
TFE R
command.
Use the
TFE P
command to preload or change the values of the through fault
event accumulated data, as shown in
. Enter these values in percent
for each phase, up to a maximum value of 100.0 percent.
=>>TFE P
Winding 1 Total Accumulated Percentage of Through Fault Capability:
A_Phase = 0.00? 60.20
B_Phase = 0.00? 56.0
C_Phase = 0.00? 52
Are you sure (Y,N)? Y
Command Completed
=>>
Figure 5.20
Preload the Values of the Accumulated Data
Table 5.11
Through-Faults Events Report Messages
Message
Cause
Invalid Data
The accumulated data is corrupt.
Through Fault Event Monitor Disabled
The ETHRFLT setting is NA, or evaluates to
logical 0.
Too many events - Data Lost
The memory is full.
Through Fault Event Buffer Empty
There are no event records in the nonvolatile
memory
Memory resources are low; check for
activity on other ports
There is insufficient memory to display the
event records
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...