D.24
SEL-787 Relay
Instruction Manual
Date Code 20081022
DNP3 Communications
DNP3 Documentation
Reference Data Map
shows the SEL-787 reference data map. The reference map shows
the data available to a DNP3 master. You can use the default map or the
custom DNP3 mapping functions of the SEL-787 to retrieve only the points
required by your application.
NOTE:
Dead-band changes via
Object 34 are not stored in nonvolatile
memory. Make sure to reissue the
Object 34 dead bands after a warm
(
STA C
) or cold start (power cycle).
The SEL-787 scales analog values by the indicated settings or fixed scaling
indicated in the description. Analog dead bands for event reporting use the
indicated settings, or ANADBM if you have not specified a setting.
101
1
Small Packed Binary-Coded Decimal
101
2
Medium Packed Binary-Coded Decimal
101
3
Large Packed Binary-Coded Decimal
110
all
Octet String
111
all
Octet String Event
112
All
Virtual Terminal Output Block
113
All
Virtual Terminal Event Data
N/A
No object required for the following function
codes:
13 cold start
14 warm start
23 delay measurement
13, 14, 23
a
Supported in requests from master.
b
May generate in response to master.
c
Decimal.
d
Hexadecimal.
e
Default variation.
Table D.11
SEL-787 DNP Object List
(Sheet 5 of 5)
Obj. Var.
Description
Request
a
Response
b
Funct. Codes
c
Qual. Codes
d
Funct. Codes
c
Qual. Codes
d
Table D.12
DNP3 Reference Data Map
(Sheet 1 of 2)
Object
Labels
Description
Binary Inputs
01, 02
STFAIL
STWARN
STSET
Enabled–T06_LED
Relay Word Elements Target Row 0 (see
)
50P11T–TUTCH
PFL
Power Factor Leading for Three-Phase Currents
0
Logical 0
1
Logical 1
Binary Outputs
10, 12
RB
xx
Remote Bits (
xx
= 01–32)
CC
x
Breaker Close Bits (
x
= 1–2)
OC
x
Breaker Open Bits (
x
= 1–2)
Counters
20, 22
SC
xx
SEL
OGIC
Counter Values (
xx
= 01–32)
GROUP
Active Settings Group
NOTE:
Although not shown as part
of the reference maps you may use
any Relay Word bit label when
creating custom maps.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...