4.64
SEL-787 Relay
Instruction Manual
Date Code 20081022
Protection and Logic Functions
Demand Metering
The demand current level settings are applied to demand current meter outputs
as shown in
. For example, when residual ground demand current
IGD goes above corresponding demand pickup GNDEMP, Relay Word bit
GNDEM asserts to logical 1. Use these demand current logic outputs
(PHDEM, GNDEM, and 3I2DEM) to alarm for high loading or unbalance
conditions.
Figure 4.41
Demand Current Logic Outputs
The demand values are updated approximately once a second. The relay stores
peak demand values to nonvolatile storage every six hours (it overwrites the
previous stored value if it is exceeded). Should the relay lose control power, it
will restore the peak demand values saved by the relay.
Demand metering peak recording is momentarily suspended when
SEL
OGIC
control equation setting FAULT is asserted (= logical 1).
The differences between thermal and rolling demand metering are explained
in the following discussion.
Table 4.23
Demand Meter Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
ENABLE DEM MTR
OFF, W1, W2
EDEM := OFF
DEMAND MTR TYPE
THM, ROL
DEMTY := THM
DEM TIME CONSTNT
5, 10, 15, 30, 60 min
DMTC := 5
PH CURR DEM LVL
OFF, 0.50-16.00 A
a
OFF. 0.10-3.20 A
b
a
For Inom = 5 A.
b
For Inom = 1 A.
PHDEMP := 5.00
PHDEMP := 1.00 b
RES CURR DEM LVL
OFF, 0.50-16.00 A
OFF, 0.10-3.2 A
GNDEMP := 1.00
GNDEMP := 0.20
3I2 CURR DEM LVL
OFF, 0.50-16.00 A
OFF, 0.10-3.2 A
3I2DEMP := 1.00
3I2DEMP := 0.20
PHDEM
Relay
Word
Bits
Demand Current
Pickup Settings
(A Secondary)
IBD
IAD
IAWn
ICD
Analog
Quantities
Demand
Currents
Instantaneous
Currents
Serial Port
Command
Demand Function
Maximum
Current
Logic
Thermal (EDEM = THM)
or
Rolling (EDEM = ROL)
Reset
Demand
PHDEMP
IGD
Reset
Demand
Thermal (EDEM = THM)
or
Rolling (EDEM = ROL)
GNDEM
GNDEMP
IGWn
(residual)
Demand Function
3I2D
Reset
Demand
Thermal (EDEM = THM)
or
Rolling (EDEM = ROL)
3I2DEM
3I2DEMP
3I2Wn
MET RD
Demand Function
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...