2
SEL-787 Relay Command Summary
SEL-787 Relay
Instruction Manual
Date Code 20081022
EVE DIF1
n
Show differential element 1 event report number
n
, with 1/4-cycle resolution.
EVE DIF2
n
Show differential element 2 event report number
n
, with 1/4-cycle resolution.
EVE DIF3
n
Show differential element 3 event report number
n
, with 1/4-cycle resolution.
EVE R
n
Show raw analog data event report number
n
, with 1/16-cycle resolution, same as
EVE
n
R
.
FIL DIR
Return a list of files.
FIL READ
filename
Transfer settings file
filename
from the relay to the PC.
FIL SHOW
filename
Filename 1 displays contents of the file filename.
GOO
k
Display transmit and receive GOOSE messaging information. Enter number
k
to scroll the GOOSE data
k
times on the screen.
GRO
Display active group setting.
HEL
Display a short description of selected commands.
HIS
n
Show
summary
of
n
latest event reports, where
n
= 1 is the most recent entry. If
n
is not specified, all event
report summaries are displayed.
HIS C or R
Clear or reset history buffer.
IRIG
Force synchronization of internal control clock to IRIG-B time-code input.
LDP
Display signal profile data.
LDP C
Clear signal profile data.
MAC
Display the MAC address of the Ethernet port (PORT 1).
MET
Display fundamental metering data. (Can also use
MET F
.)
MET
k
Display fundamental metering data
k
times, where
k
is between 1 and 32767.
MET AI
Display analog input (transducer) data.
MET DEM
k
Display demand metering data, in primary amperes. Enter number k to scroll metering k times on screen.
MET DIF
k
Display differential metering data. Enter number k to scroll metering k times on screen.
MET E
Display energy metering data.
MET H
Generate harmonic report for all input currents and voltages, showing first to fifth harmonic levels and
%THD (total harmonic distortion).
MET M
Display minimum and maximum metering data.
MET MV
Display SEL
OGIC
math variable data.
MET PEA
k
Display peak demand metering data, in primary amperes. Enter number
k
to scroll metering
k
times on
screen.
MET PM
Display synchrophasor metering data.
MET RD
Reset demand metering values.
MET RE
Reset energy metering data.
MET RM
Reset minimum and maximum metering data.
MET RMS
Display
RMS
metering data.
MET RP
Reset peak demand metering values.
MET T
Display
RTD
metering data.
Serial Port Command
Command Description
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...