1.4
SEL-787 Relay
Instruction Manual
Date Code 20081022
Introduction and Specifications
Applications
For all SEL-787 mounting accessories for competitor products’ replacement,
including adapter plates, visit http://www.selinc.com/MountingAccessories.
Applications
Refer to
for various applications and their related
connection diagrams. The following is a list of possible application scenarios:
➤
Two-winding transformer protection with current differential
and overcurrent elements and through-fault monitor
➤
Two-winding transformer protection with current differential
and overcurrent elements and through-fault monitor with
optional restricted earth fault protection (REF) and neutral-
overcurrent protection
➤
Two-winding transformer protection with current differential
and overcurrent elements and through-fault monitor with
optional voltage elements, power elements, and frequency
elements
➤
Two-winding transformer protection with current differential
and overcurrent elements and through-fault monitor with
optional internal or external RTD inputs module
Getting Started
IMPORTANT:
Upon relay initial
power up or Port 1 setting changes or
Logic setting changes, the user may
have to wait up to two minutes before
an additional setting change can
occur. Note that the relay is functional
with protection enabled, as soon as
the
ENABLED LED
comes ON (about 5–10
seconds from power up).
Understanding basic relay operation principles and methods will help you use
the SEL-787 effectively. This section presents the fundamental knowledge
you need to operate the SEL-787, organized by task. These tasks help you
become familiar with the relay and include the following:
➤
Powering the relay
➤
Establishing communication
➤
Checking relay status
➤
Setting the date and time
Perform these tasks to gain a fundamental understanding of relay operation.
Powering the Relay
Power the SEL-787 with 125/250 Vac/dc or 24/48 Vdc, depending on the part
number.
➤
Observe proper polarity, as indicated by the
+/H
(terminal
A01
)
and the
–/N
(terminal
A02
) on the power connections.
➤
Connect the ground lead; see
.
➤
Once connected to power, the relay does an internal self-check
and the
ENABLED
LED illuminates.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...