7.32
SEL-787 Relay
Instruction Manual
Date Code 20081022
Communications
SEL ASCII Protocol and Commands
=>>
SHO <Enter>
Group 1
Relay Settings
ID Settings
RID := SEL-787
TID := TRNSFRMR RELAY
Config Settings
W1CT := WYE W2CT := WYE CTR1 := 100
CTR2 := 1000 MVA := 50.0 ICOM := N
VWDG1 := 138.00 VWDG2 := 13.80 CTRN1 := 120
PTR := 120.00 VNOM := 13.80 DELTA_Y := DELTA
VIWDG := 2 SINGLEV := N
DIFF ELEMENT
E87 := Y TAP1 := 2.09 TAP2 := 2.09
O87P := 0.30 87AP := 0.15 87AD := 5.0
SLP1 := 25 SLP2 := 50 IRS1 := 3.0
U87P := 10.0 PCT2 := 15 PCT4 := OFF
PCT5 := 35 TH5P := OFF HRSTR := Y
HBLK := N
Restricted Earth FLT
REF1POL := OFF
REF1TC := 1
50REF1P := 0.25
WDG1 Max Ph IOC
50P11P := 10.00 50P11D := 0.00
50P11TC := 1
50P12P := 10.00 50P12D := 0.00
50P12TC := 1
50P13P := 10.00 50P13D := 0.00
50P13TC := 1
50P14P := 10.00 50P14D := 0.00
50P14TC := 1
WDG1 Res IOC
50G11P := OFF 50G12P := OFF
WDG1 Neg Seq IOC
50Q11P := OFF 50Q12P := OFF
WDG1 Max Ph TOC
51P1P := 6.00 51P1C := U3 51P1TD := 3.00
51P1RS := N 51P1CT := 0.00 51P1MR := 0.00
51P1TC := 1
WDG1 Res TOC
51G1P := 0.50 51G1C := U3 51G1TD := 1.50
51G1RS := N 51G1CT := 0.00 51G1MR := 0.00
51G1TC := 1
Table 7.44
SHOW Command (Show/View Settings)
Command
Description
Access Level
SHO
s
Show Group settings.
1
SHO L
s
Show general logic settings.
1
SHO G
s
Show global settings.
1
SHO P
n s
Show serial port settings.
n
specifies the port
(
1
,
2
,
3
,
4
,
or
F
);
n
defaults to the active port if not listed.
1
SHO R
s
Show report settings such as Sequential Events
Recorder (SER) and Event Report (ER) settings.
1
SHO F
s
Show front-panel settings.
1
SHO M
s
Show Modbus User Map settings.
1
SHO DNP
n
Display DNP3 data map settings for map n
(n = 1, 2, or 3)
1
Table 7.45
SHOW Command Format
Parameter
Description
s
Appends
s
, the name of the specific setting you want to view, and jumps to
this setting. If
s
is not entered, the relay starts at the first setting.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...