4.91
Date Code 20081022
Instruction Manual
SEL-787 Relay
Protection and Logic Functions
Global Settings (SET G Command)
Figure 4.60
AC Mode Processing
shows a timing diagram for the ac mode of operation. On the
rising edge of IN101R, the pickup timer starts timing (points marked 1 in
). If IN101R deasserts (points marked 2 in
) before
expiration of the pickup time setting, Relay Word bit IN101 does not assert,
and remains at logical 0. If, however, IN101R remains asserted for a period
longer than the pickup timer setting, then Relay Word bit IN101 asserts to a
logical 1.
Figure 4.61
Timing Diagram for Debounce Timer Operation When Operating
in AC Mode
Deassertion follows the same logic. On the falling edge of IN101R, the
dropout timer starts timing. If IN101R remains deasserted for a period longer
than the dropout timer setting, then Relay Word bit IN101 deasserts to a
logical 0.
shows the settings prompt, setting range, and factory default
settings for a card in Slot
C
. See the
for a complete
list of input debounce settings.
Table 4.39
Slot C Input Debounce Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
IN301 Debounce
AC, 0–65000 ms
IN301D := 10
IN302 Debounce
AC, 0–65000 ms
IN302D := 10
IN303 Debounce
AC, 0–65000 ms
IN303D := 10
IN304 Debounce
AC, 0–65000 ms
IN304D := 10
IN305 Debounce
AC, 0–65000 ms
IN305D := 10
IN306 Debounce
AC, 0–65000 ms
IN306D := 10
IN307 Debounce
AC, 0–65000 ms
IN307D := 10
IN308 Debounce
AC, 0–65000 ms
IN308D := 10
2 ms
16 ms
IN101
Relay
Word
Bit
IN101R
Debounce Timer
IN101R
2 ms
IN101R Deasserted;
DDOT Counts
IN101R Deasserted;
DDOT Counts
Dropout Time
(16 ms)
Debounce Dropout
Timer Expires;
Relay Word Bit
IN101 Deasserts
Debounce Pickup
Timer Expires;
Relay Word Bit
IN101 Asserts
IN101R Asserted;
DPUT Counts
IN101R Asserted;
DPUT counts
Relay Word
Bit IN101
1
2
1
1 1
1 1
2
2 2
2 2
DPUT = Debounce Pickup Timer
DDOT = Debounce Dropout Timer
1 = Rising Edge: DPUT Counts
2 = Falling Edge: DDOT Counts
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...