D.17
Date Code 20081022
Instruction Manual
SEL-787 Relay
DNP3 Communications
DNP3 in the SEL-787
Figure D.6
Analog Input Map Entry in
AC
SEL
ERATOR
QuickSet Software
Figure D.7
AI Point Label, Scaling and Deadband in
AC
SEL
ERATOR
QuickSet
Software
The
SET DNP
x
CO_00 <Enter>
command allows you to populate the DNP
counter map with per-point dead bands. Entering these settings is similar to
defining the analog input map settings.
You can use the command
SET DNP
x
BO_00 TERSE <Enter>
to change
the binary output map
x
as shown in
. You may populate the custom
BO map with any of the 32 remote bits (RB01–RB32). You can define bit
pairs in BO maps by including a colon (:) between the bit labels.