9.7
Date Code 20081022
Instruction Manual
SEL-787 Relay
Analyzing Events
Event Reporting
Raw event reports display one extra cycle of data at the beginning of the
report.
Also, unlike the filtered report, the raw event report shows the actual relay
terminal voltage inputs so if the external connections are for DELTA input,
VA = Vab, VB = 0, VC = –Vbc (in primary volts).
Analog Event Report Column Definitions
NOTE:
is on multiple
pages.
Refer to the example analog event report in
to view event report
columns. This example event report displays rows of information each 1/4
cycle. Retrieve this report with the
EVE
command.
The columns contain analog values, including ac current, ac voltage, and
frequency, followed by base model input and output information.
summarizes the analog event report columns.
Note that the ac values change from plus to minus (–) values in
indicating the sinusoidal nature of the waveforms.
Table 9.2
Analog Event Report Columns Definitions
Column
Heading
Column
Symbols
Description
IAW1
Current measured by channel IA, Winding 1 (primary A)
IBW1
Current measured by channel IB, Winding 1 (primary A)
ICW1
Current measured by channel IC, Winding 1 (primary A)
IGW1
Residual current (IAW1 + IBW1 + ICW1, primary A), dis-
played only when no voltages are shown
IAW2
Current measured by channel IA, Winding 2 (primary A)
IBW2
Current measured by channel IB, Winding 2 (primary A)
ICW2
Current measured by channel IC, Winding 2 (primary A)
IGW2
Residual current (IAW2 + IBW2 + ICW2, primary A), dis-
played only when no voltages are shown
IN
Current measured by channel IN (primary A) when neutral
CT is present
VAN
or
VAB
Voltage measured by channel VAN or VAB (primary V),
requires voltage input
VBN
or
VBC
Voltage measured by channel VBN or VBC (primary V),
requires voltage input
VCN
or
VCA
Voltage measured by channel VCN or VCA calculated from
VAB and VBC (primary V), requires voltage input
In
12
1
2
b
IN101 AND NOT IN102
NOT IN101 AND IN102
IN101 AND IN102
Out
12
1
2
b
OUT101 AND NOT OUT102
NOT OUT101 AND OUT102
OUT101 AND OUT102
Out
3
3
OUT103
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...