Testing and Troubleshooting
Testing Tools
Use the
TARGET
command to view the state of relay control inputs, relay
outputs, and relay elements individually during a test. The
TARGET
command is available at the serial ports and the front panel. See
and
Section 8: Front-Panel Operations
.
Low-Level Test
Interface
The SEL-787 has a low-level test interface on the 6 ACI current card (Slot Z)
and 1 ACI Neutral current card or 1 ACI/3 AVI current/voltage card (Slot E).
You can test the relay in either of two ways: conventionally by applying ac
signals to the relay inputs or by applying low magnitude ac voltage signals to
the test interface on the printed circuit boards.
The SEL-RTS Low-Level Relay Test System can be used to provide signals to
test the relay.
shows the Test Interface connectors.
Figure 10.1
Low-Level Test Interface (J2 and J3)
Note that there are two options for the Slot E for low level interface:
➤
The 1 ACI card supports neutral current input IN only.
➤
The 1 ACI/3 AVI card supports the neutral current input IN and
three-phase ac voltage inputs VA, VB, and VC.
Connector J3 is the same in both options.
shows the signal scale factor information used by the SEL-5401
program for the calibrated inputs.
Table 10.1
Resultant Scale Factors for Inputs
Channel
Label
Circuit Board &
Connector
SEL-5401
Channel No.
Nominal Input
Scale Factor
(A/V or V/V)
IAW1
6 ACI card /J2
1
5 A/1 A
106.14 / 21.23
IBW1
6 ACI card /J2
2
5 A/1 A
106.14 / 21.23
ICW1
6 ACI card /J2
3
5 A/1 A
106.14 / 21.23
IAW2
6 ACI card /J2
4
5 A/1 A
106.14 / 21.23
IBW2
6 ACI card /J2
5
5 A/1 A
106.14 / 21.23
ICW2
6 ACI card /J2
6
5 A/1 A
106.14 / 21.23
VA
1 ACI /3 AVI card/ J3
7
250 V
218.4
VB
1 ACI /3 AVI card/ J3
8
250 V
218.4
VC
1 ACI /3 AVI card/ J3
9
250 V
218.4
IN
1 ACI /3 AVI card/ J3
12
5 A/1 A
106.14 / 21.23
NOTE:
The SEL-RTS Relay Test
System consists of the SEL-AMS
Adaptive Multichannel Source and
SEL-5401 Test System Software.
(A) Connector J2 on 6 ACI Current Input Board
(B) Connector J3 on 1 ACI/3 AVI Current
Voltage Input Board
1
IN
VC
VB
VA
GND
GND
GND
GND
1
ICW2 IBW2 IAW2 ICW1
IBW1
IAW1
GND
GND
GND
GND
GND
GND
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...