3.4
SEL-787 Relay
Instruction Manual
Date Code 20081022
PC Software
Settings Database Management and Drivers
Terminal Logging
To create a file that contains all terminal communications with the relay, select
Terminal Logging
in the
Log
menu, and specify a file at the prompt.
AC
SEL
ERATOR
QuickSet records communications events and errors in this
file. Click
Log > Connect Log
to view the log. Clear the log by selecting
Log > Clear Connection Log
.
Drivers and Part
Number
After clicking
Tools > Terminal
, access the relay at Access Level 1. Issue the
ID
command to receive an identification report, as shown in
=>
ID <Enter>
"FID=SEL-787-R100-V0-Z001001-D20080407","0947"
"BFID=BOOTLDR-R303-V0-Z000000-D20060612","0949"
"CID=26FF","0271"
"DEVID=SEL-787","03D0"
"DEVCODE=71","030F"
"PARTNO=0787EX1B0X0X7585023X","073D"
"CONFIG=11111201","03EB"
"iedName =TEMPLATE","0380"
"type =SEL-787","028F"
"configVersion =ICD-787-R100-V0-Z001001-D20080326","0629"
=>
Figure 3.5
Device
Response to the ID Command
Locate and record the Z number (Z001001) in the FID string. The first portion
of the Z number (Z001…) determines the
AC
SEL
ERATOR
QuickSet relay
settings driver version when you are creating or editing relay settings files.
The use of the Device Editor driver version will be discussed in more detail
later in this section—see
Settings Editor (Editor Mode) on page 3.8
. Compare
the part number (
PARTNO=0787XXXXXXXXXXXXXXXX
) with the Model Option
Table (MOT) to ensure the correct relay configuration.
Settings Database Management and Drivers
AC
SEL
ERATOR
QuickSet uses a database to save relay settings.
AC
SEL
ERATOR
QuickSet contains sets of all settings files for each relay
specified in the Database Manager. Choose appropriate storage backup
methods and a secure location for storing database files.
Active Database
Change the active database to the one that needs to be modified by selecting
File > Active Database
on the main menu bar.
Database Manager
Select
File > Database Manager
on the main menu bar to create new
databases and manage records within existing databases.
Settings Database
Step 1. Open the Database Manager to access the database. Click
File
> Database Manager
. A dialog box appears.
The default database file already configured in
AC
SEL
ERATOR
QuickSet is Relay.rdb. This database contains example settings
files for the SEL products with which you can use
AC
SEL
ERATOR
QuickSet.
Step 2. Enter descriptions for the database and for each relay or relay
in the database in the
Database Description
and
Settings
Description
dialog boxes.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...