4.51
Date Code 20081022
Instruction Manual
SEL-787 Relay
Protection and Logic Functions
Voltage-Based Protection
Voltage-Based Protection
The following information applies to relay models with voltage inputs.
Undervoltage
Function
Overvoltage Function
When you connect the SEL-787 voltage inputs to phase-to-phase connected
VTs (single-phase or three-phase), as in
, the relay
provides two levels of phase-to-phase overvoltage and undervoltage elements.
When you connect the SEL-787 voltage inputs to phase-to-neutral connected
VTs (single-phase or three-phase), as in
, the relay
provides two levels of phase-to-neutral overvoltage and undervoltage
elements. The SEL-787 also includes two levels of negative-sequence
overvoltage elements. Use these elements for alarm or trip when three-phase
voltage inputs (wye or delta) are connected to the relay.
Each of the elements has an associated time delay. You can use these elements
as you choose for tripping and warning.
show the
logic diagram for the undervoltage and overvoltage elements, respectively. To
disable any of these elements, set the level settings equal to OFF.
Table 4.18
Undervoltage Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PHASE UV LEVEL
OFF, 12.5–300.0 V
27P1P := OFF
PHASE UV DELAY
0.0–120.0 sec
27P1D := 0.5
PHASE UV LEVEL
OFF, 12.5–300.0 V
27P2P := OFF
PHASE UV DELAY
0.0–120.0 sec
27P2D := 5.0
Table 4.19
Overvoltage Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PHASE OV LEVEL
OFF, 12.5–300.0 V
59P1P := OFF
PHASE OV DELAY
0.0–120.0 sec
59P1D := 0.5
PHASE OV LEVEL
OFF, 12.5–300.0 V
59P2P := OFF
PHASE OV DELAY
0.0–120.0 sec
59P2D := 5.0
NSEQ OV LEVEL
OFF, 12.5–300.0 V
59Q1P := OFF
NSEQ OV DELAY
0.0–120.0 sec
59Q1D := 0.5
NSEQ OV LEVEL
OFF, 12.5–300.0 V
59Q2P := OFF
NSEQ OV DELAY
0.0–120.0 sec
59Q2D := 5.0
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...