- 206 -
Troubleshooting
8
■
Specification 2
■
• In case of occurring the error during the operation, error mode is displayed at the outdoor unit PCB display.
■
• Error display number each means the following error.
●
Display method
●
101~650(Error) : "E", 700~900(Protection error) : "P", Error occurred indoor unit address : "A"
●
_ In case of the indoor unit error
●
_
After displaying E on SEG1 and error number on SEG2,3,4 with decimal, display the number of indoor unit to "A".
●
_
Namely, in case of occurring error 99 on indoor unit number 33, E99
→
A31
→
REPEAT.
●
_ In case of the indoor unit error and others
●
_
After displaying E on SEG1 it is disappeared, and then error number is displayed on SEG2,3,4 with decimal.
●
_
1) In case of error 223
●
_ 1)
E223
→
E223
→
REPEAT
●
_
2) In case of error 701
●
_ 1)
P701
→
P701
→
REPEAT
■
Outdoor unit display at the detection of an error
Error range
Error part
101~120
121~150
151~200
201~220
221~400
401~550
551~600
601~650
701~900
Indoor unit
Outdoor unit
OPTION
Others
Error
Sensor
Communication
Others
Communication
Sensor
Protection control
Others
Option
Low Level
error
error
error
error
error
Self diagnosis
error
Risk Error
Error Display
Remark
Contents
SEG 1
SEG 2,3,4
NUMBER
101~200
Communication error between the indoor unit and the Panel
Indoor unit sensor related error
Indoor unit room temp. sensor open/short error
Indoor unit EVAP IN sensor open/short error
Indoor unit EVAP OUT sensor open/short error
Indoor unit EVAP IN sensor breakaway
Indoor unit EVAP OUT sensor breakaway
Simultaneous breakaway of Indoor unit EVAP IN/OUT sensor
Auxiliary (electric) heater sensor 1 error
Auxiliary (electric) heater sensor 2 error
Auxiliary (electric) heater sensor 3 error
Shutter sensor error
Perfect fan sensor error
Indoor unit related error
Indoor unit EEV open failure
Indoor unit EEV close failure
Indoor unit float S/W detection
Indoor fan error
Indoor unit related error
PAC
PAC
PAC
~
~
DB98-17816A(1)_8 3/2/04 9:35 AM Page 206
Summary of Contents for DVM Series
Page 76: ... 75 Memo ...
Page 112: ......
Page 113: ......
Page 156: ... 155 Memo ...
Page 280: ... 279 Exploded Views and Parts List 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 281: ... 280 Exploded Views and Parts List 9 F Type cont 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 285: ... 284 Exploded Views and Parts List 9 ...
Page 287: ... 286 Exploded Views and Parts List 9 31 1 31 4 31 2 31 5 31 6 31 3 57 1 57 2 58 G Type cont ...
Page 291: ... 290 Exploded Views and Parts List 9 ...
Page 292: ... 291 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 31 3 62 1 62 2 63 1 63 2 ...
Page 298: ... 297 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 61 1 61 2 62 1 65 2 31 3 ...
Page 358: ... 357 Memo ...
Page 361: ... 360 Wiring Diagram 10 10 1 2 4 way cassette type Cooling only AVMCC ...
Page 362: ... 361 Heat pump AVMCH ...
Page 369: ... 368 Wiring Diagram 10 070F This Document can not be used without Samsung s authorization ...
Page 370: ... 369 Wiring Diagram 080 100 This Document can not be used without Samsung s authorization ...
Page 371: ... 370 Wiring Diagram 10 100F This Document can not be used without Samsung s authorization ...
Page 373: ... 372 Wiring Diagram 10 080 100 This Document can not be used without Samsung s authorization ...
Page 374: ... 373 Wiring Diagram 100F This Document can not be used without Samsung s authorization ...
Page 385: ... 384 Schematic Diagram 11 050 This Document can not be used without Samsung s authorization ...
Page 389: ... 388 Memo ...