- 153 -
Refrigerating Cycle Diagram
6-2-7. Main parts status
1. Digital scroll compressor
The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps
2. Accumulator
To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back).
3. Receiver
To reduce the noise by flowing the high pressure liquid refrigerant to the high pressure pipe and to control
the amount of refrigerant during the individual operation of indoor unit.
4. Solenoid valve (PWM)
It is installed at the top of digital scroll compressor and at the low pressure pipe, which is used for operating the digital scroll
compressor. When the valve is open, the digital scroll compressor keeps the state of
unloading.
5. Solenoid valve (HGBV)
When the low pressure gets lower, the valve is open by the low pressure safety device. The valve is open in order to reduce
the load at the start of compressor and when the system stops and then keep the balance of low pressure.
6. Solenoid valve (LBV)
When the compressor is overheated, it actuates to lower the temperature of compressor for stable operation.
7. Solenoid valve (VBV)
The valve is open in order to reduce the load at the start of compressor and when the system stops and then keeps the
balance of low pressure.
8. High pressure switch (HPS)
To stop the system for the system protection when the high pressure exceeds the set value.
9. Temperature sensor (DTS, Discharge Temperature Sensor)
9.
It is the means to measure the refrigerant temperature of compressor outlet which is used as the data
for control of compressor.
10. Temperature sensor (COS, Condenser Out Sensor)
10.
When heating, used for defrost control by sensing outdoor heat exchanger temperature.
11. Temperature sensor (OATS, Outdoor Air Temperature Sensor)
10.
To measure the outdoor temperature which is used for the determination of start method.
12. Fixed scroll compressor
10.
The fixed capacity type compressor.
DB98-17816A(1)_6~7 3/2/04 9:33 AM Page 153
Summary of Contents for DVM Series
Page 76: ... 75 Memo ...
Page 112: ......
Page 113: ......
Page 156: ... 155 Memo ...
Page 280: ... 279 Exploded Views and Parts List 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 281: ... 280 Exploded Views and Parts List 9 F Type cont 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 285: ... 284 Exploded Views and Parts List 9 ...
Page 287: ... 286 Exploded Views and Parts List 9 31 1 31 4 31 2 31 5 31 6 31 3 57 1 57 2 58 G Type cont ...
Page 291: ... 290 Exploded Views and Parts List 9 ...
Page 292: ... 291 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 31 3 62 1 62 2 63 1 63 2 ...
Page 298: ... 297 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 61 1 61 2 62 1 65 2 31 3 ...
Page 358: ... 357 Memo ...
Page 361: ... 360 Wiring Diagram 10 10 1 2 4 way cassette type Cooling only AVMCC ...
Page 362: ... 361 Heat pump AVMCH ...
Page 369: ... 368 Wiring Diagram 10 070F This Document can not be used without Samsung s authorization ...
Page 370: ... 369 Wiring Diagram 080 100 This Document can not be used without Samsung s authorization ...
Page 371: ... 370 Wiring Diagram 10 100F This Document can not be used without Samsung s authorization ...
Page 373: ... 372 Wiring Diagram 10 080 100 This Document can not be used without Samsung s authorization ...
Page 374: ... 373 Wiring Diagram 100F This Document can not be used without Samsung s authorization ...
Page 385: ... 384 Schematic Diagram 11 050 This Document can not be used without Samsung s authorization ...
Page 389: ... 388 Memo ...