Troubleshooting
8
Error Display
Remark
Contents
SEG 1
SEG 2,3,4
SUMP TEMP FIXED 1 sensor error OPEN/SHORT
_ Detected when the outdoor temperature is over -10˚C
_ ERROR LEVEL : OVER 4.95V(-30˚C), BELOW 0.5V(151˚C)
SUMP TEMP FIXED 2 sensor error OPEN/SHORT
_ Detected when the outdoor temperature is over -10˚C
_ ERROR LEVEL : OVER 4.95V(-30˚C), BELOW 0.5V(151˚C)
SUMP TEMP FIXED 3 sensor error OPEN/SHORT
_ Detected when the outdoor temperature is over -10˚C
_ ERROR LEVEL : OVER 4.95V(-30˚C), BELOW 0.5V(151˚C)
High pressure sensor error OPEN/SHORT
Detected when the compressor is ready to operate.
_ SHORT error : BELOW O.4V
_ OPEN error : detected over 4.2V
Low pressure sensor error OPEN/SHORT
Detected when the compressor is ready to operate.
_ SHORT error: BELOW 0.4V
_ OPEN error: detected over 4.7V
High pressure sensor breakaway
Low pressure sensor breakaway
Outdoor protection control/self diagnosis related error
Outdoor unit freezing detection 1
Outdoor unit freezing detection 2
Outdoor unit freezing detection 3-freezing COMP DOWN
Outdoor unit overload 1 protection control error
Outdoor unit overload 2 protection control error
Outdoor unit overload 3 protection control error
Compressor down by high pressure sensor protection control 1
Compressor down by high pressure sensor protection control 2
Compressor down by high pressure sensor protection control 3
Compressor down by low pressure sensor protection control 1
Compressor down by low pressure sensor protection control 2
Compressor down by low pressure sensor protection control 3
Outdoor unit SUMP DOWN 1 protection control
Outdoor unit SUMP DOWN 2 protection control
Outdoor unit SUMP DOWN 3 protection control
Outdoor unit discharge temperature 1 protection control
~
DB98-17816A(1)_8 3/2/04 9:35 AM Page 208
Summary of Contents for DVM Series
Page 76: ... 75 Memo ...
Page 112: ......
Page 113: ......
Page 156: ... 155 Memo ...
Page 280: ... 279 Exploded Views and Parts List 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 281: ... 280 Exploded Views and Parts List 9 F Type cont 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 285: ... 284 Exploded Views and Parts List 9 ...
Page 287: ... 286 Exploded Views and Parts List 9 31 1 31 4 31 2 31 5 31 6 31 3 57 1 57 2 58 G Type cont ...
Page 291: ... 290 Exploded Views and Parts List 9 ...
Page 292: ... 291 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 31 3 62 1 62 2 63 1 63 2 ...
Page 298: ... 297 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 61 1 61 2 62 1 65 2 31 3 ...
Page 358: ... 357 Memo ...
Page 361: ... 360 Wiring Diagram 10 10 1 2 4 way cassette type Cooling only AVMCC ...
Page 362: ... 361 Heat pump AVMCH ...
Page 369: ... 368 Wiring Diagram 10 070F This Document can not be used without Samsung s authorization ...
Page 370: ... 369 Wiring Diagram 080 100 This Document can not be used without Samsung s authorization ...
Page 371: ... 370 Wiring Diagram 10 100F This Document can not be used without Samsung s authorization ...
Page 373: ... 372 Wiring Diagram 10 080 100 This Document can not be used without Samsung s authorization ...
Page 374: ... 373 Wiring Diagram 100F This Document can not be used without Samsung s authorization ...
Page 385: ... 384 Schematic Diagram 11 050 This Document can not be used without Samsung s authorization ...
Page 389: ... 388 Memo ...