Troubleshooting
8
8-2-76. Indoor unit EEV CLOSE error
Indoor unit display
Outdoor unit display
Judgment method
Causes
1
st
detection : (Displayed only outdoor unit)
2
nd
detection : x x x (x x x : Indoor unit address occurred error)
(Operation)
(Timer)
(Fan)
(Filter)
(Removing frost)
- Refer to the below judge method
- Indoor unit EEV operation defect (EEV does not open.)
1. Judge method (The following conditions should be satisfied for more than 20 minutes.)
1) In cooling mode
2) In heating mode (All following conditions should be satisfied)
2)
(1) More than 2 indoor units are operating in THERMO ON heating mode.
2)
(2) The average of high pressure
≥
18kg/cm
2
g
2)
(3) After 5 minutes from the completion of safety start, the condition of indoor unit T(EVAP_in) < T(Room) + 3˚C and
T(EVAP_out) < T(Room) + 3˚C is maintained for 5 minutes.
2. Check method
1) Check whether the EEV wire is connected correctly to the indoor unit PCB.
2) Check whether the EEV coil is inserted to the main body correctly.
3) After pressing the reset key(K3) of outdoor unit, check if the same error is occurred.
3)
●
If it is the CLOSE error, operate the corresponding indoor unit.
3)
●
If it is OPEN error, turn the power of corresponding indoor unit off to check.
4) If there is no trouble for the above checks, replace the EEV of the corresponding indoor unit.
3)
●
Since the replacement of EEV is the inconvenient work to collect the all refrigerant in the system, be sure to check
the above items before replacing EEV.
Tcond, out - Tair, out > 3°C
Tair, in - Teva, in > 4°C
Tair, in - Teva, out > 4°C
Compressor running &
indoor unit on and thermo on
Error contents
OK
NO
NO
OK
Department error of indoor unit EVAP IN sensor
DB98-17816A(1)_8 3/2/04 9:35 AM Page 244
Summary of Contents for DVM Series
Page 76: ... 75 Memo ...
Page 112: ......
Page 113: ......
Page 156: ... 155 Memo ...
Page 280: ... 279 Exploded Views and Parts List 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 281: ... 280 Exploded Views and Parts List 9 F Type cont 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Page 285: ... 284 Exploded Views and Parts List 9 ...
Page 287: ... 286 Exploded Views and Parts List 9 31 1 31 4 31 2 31 5 31 6 31 3 57 1 57 2 58 G Type cont ...
Page 291: ... 290 Exploded Views and Parts List 9 ...
Page 292: ... 291 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 31 3 62 1 62 2 63 1 63 2 ...
Page 298: ... 297 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 61 1 61 2 62 1 65 2 31 3 ...
Page 358: ... 357 Memo ...
Page 361: ... 360 Wiring Diagram 10 10 1 2 4 way cassette type Cooling only AVMCC ...
Page 362: ... 361 Heat pump AVMCH ...
Page 369: ... 368 Wiring Diagram 10 070F This Document can not be used without Samsung s authorization ...
Page 370: ... 369 Wiring Diagram 080 100 This Document can not be used without Samsung s authorization ...
Page 371: ... 370 Wiring Diagram 10 100F This Document can not be used without Samsung s authorization ...
Page 373: ... 372 Wiring Diagram 10 080 100 This Document can not be used without Samsung s authorization ...
Page 374: ... 373 Wiring Diagram 100F This Document can not be used without Samsung s authorization ...
Page 385: ... 384 Schematic Diagram 11 050 This Document can not be used without Samsung s authorization ...
Page 389: ... 388 Memo ...