Chapter 12: Firmware Upgrade
181
STEP (E): Repeat Steps (B) and (D) for the Other Clusters
After finishing the upgrade of one cluster, continue to upgrade the
remaining clusters.
To upgrade the other clusters, repeat the following procedure on
each cluster
1. Disconnect the Cat5 cable attached with the USB-to-RS485 cable
from the HubPac cluster on which the upgrade has finished.
2. Reconnect the Cat5 cable to the server connection port of “another
cluster” on the same HubPac, as described in
STEP (B): Connect
One Cluster of the HubPac to the PC
(on page 174).
3. Click
Send to Paragon
in the
Paragon Update
window to upgrade the
connected cluster. The procedure is the same as those described in
STEP (D): Launch the Paragon Update Utility
(on page 180).
Upon upgrading 8 clusters successfully, the P2-HubPac firmware update
is complete.