Chapter 8: P2ZCIMs and Z-CIMs
132
7. Press
Enter
and type
RefreshPZ
.
8. Press
Enter
again.
9. Press
S
to refresh the chain.
10. Press
F2
to go to the Selection Menu and verify that channel order of
the chain has been refreshed.
Important: Please follow the guideline here to ensure that there is
enough power to support all P2ZCIMs in a chain.
For Paragon I UMT242, 442, 832 and 1664 with hardware III and
Paragon II firmware, and Paragon II switches, in chains up to 20
individual P2ZCIM units at least one P2ZCIM must be powered ON; in
P2ZCIM chains from 21 to 42 P2ZCIM units, at least 15 P2ZCIMs must
be powered ON.
P2ZCIM LED Status
The LED on each P2ZCIM indicates its operational state:
•
If the LED blinks rapidly: P2ZCIM does not have a confirmed
Communication Address.
•
If the LED is primarily off and blinks on every two (2) seconds: P2ZCIM
has a confirmed Communication Address but is not switched to that
Address.
•
If the LED is on and blinks on/off rapidly when there is
keyboard/mouse traffic: CIM has a confirmed Communication Address
and is switched to that Address.
Note: The P2ZCIM blinks from time to time even if there is no
keyboard/mouse traffic, which demonstrates that the P2ZCIM is
operating normally and not locked.