ESPLXD-ET Controller
Appendix
Electrical Requirement Code of Magnetic
Solenoid
Activation Time [ms]
X
Y
Holding Voltage [Volts]
30
3
3
1.2
40
4
4
1.7
50
5
5
2.3
60
6
6
2.9
70
7
7
3.5
80
8
8
4.0
90
9
9
4.6
100
A
A
5.2
110
B
B
5.8
120
C
C
6.3
130
D
D
6.9
140
E
E
7.5
150
F
F
8.1
SWITCH CODE DEFINITION 59 F, X, Y, 0
Use the chart above to select a suitable electrical code for special
solenoid (valve) types.
b
b
NOTE:
To find a switch code that works with your valve, you may
need to use the trial and error method.
Example:
Arrows in chart show:
Activation Time =
40
ms. (milliseconds)
Holding Voltage =
2.3
volts
Switch Code
=
59F450
If the solenoid opens but will not stay open, the holding voltage may
be too low. Here, you would change the fifth digit of the code.
Example:
Arrows in chart show:
Activation Time =
50
ms.
Holding Voltage =
5.2
Volts
Switch Code
=
59F5AO
If the solenoid opens but will not stay open, the holding voltage may
be too low. Here, you would change the fifth digit of the code.