SEEF and SELF Settings and Actions
To most effectively use FloWatch, you will want to first set your SEEF
and SELF thresholds and actions. SEEF stands for Seek and Eliminate
Excessive Flow and deals with how you want your controller to respond
when excessive flow is occurring, as might be the case with a mainline
break or a valve which is stuck in the open position. SELF stands for Seek
and Eliminate Low Flow and deals with what the controller should do
when low flow is present, as might be the case during a pump failure,
municipal water supply issue or when a valve fails to open.
Set Up and Configure SEEF and SELF
b
g
Turn the controller dial to Module Programming.
A
The Smart Module PGM screen appears with Flow Smart Module
selected; press Next.
B
The Flow Smart Module PGM screen appears. Use the Down
Arrow to select FloWatch; then press Next.
a
b
C
The FloWatch screen appears with SEEF/SELF Settings selected;
press Next.
D
The SEEF Settings screen appears with high flow threshold
selected, allowing you to set the top limit (between 105-200%) of
station flow rate that must be achieved to be considered excessive.
Press the + and – buttons to set the High flow Threshold; then
press Next.
b
l
Press and HOLD buttons to accelerate settings for percentages.
b
b
NOTE:
Consider using the default setting of 130% (or higher) for
SEEF high flow threshold. Using a lower percentage can result in
false alarms due to normal hydraulic variability.
c
d
E
Settling Time is selected, allowing you to set the minimum time
(from 1-10 minutes) that a flow rate must remain at (or above) the
threshold before the controller will issue an alarm or take action.
Press the + and – buttons to set the Settling Time; then press Next.