The SELF Actions screen appears, allowing you to set the
controller’s behavior when a SELF condition exists.
A.
Diagnose and Eliminate allows the controller to determine if the
low flow condition is due to a problem on the mainline (affects
all valves in FloZone) or downstream of one of the valves that
was running when the low flow condition was detected. The
controller will eliminate the low flow condition by closing the
FloZone master valve(s) to eliminate a mainline problem or
closing the problem valve to eliminate a problem with a station.
B.
Shut Down and Alarm instructs the controller to shut down
the master valve(s) on the FloZone when a low flow condition
is detected. The controller will not attempt to diagnose if the
problem is on the mainline or downstream of a valve.
C.
Alarm Only allows the controller to issue an alarm condition, but
take no other action.
Press the + and – buttons to set the SELF Action; then press Next.
J
The Delay to Re-Enable screen appears, allowing you to select
how long (from 0 to 24 hours) before your system is re-enabled
and program starts are allowed.
b
b
NOTE:
If you select a Delay to Re-Enable time of 00:00, the
controller will not attempt to start irrigation again until you have
cleared all SEEF and SELF alarms.
Press the + and – buttons to set hours before Re-Enable; then
press Next.
b
l
Press and HOLD buttons to accelerate settings for hours and
minutes.
b
b
NOTE:
If the selected action for
both
SEEF and SELF is Alarm
Only, then the system is not disabled and the Delay to Re-Enable
screen will not be shown.
i
j
K
Press the + and – buttons to set minutes before Re-Enable; then
press Next.
k
b
b
NOTE:
SEEF and SELF settings are not active until FloWatch is
activated. You may also wish to temporarily disable FloWatch
occasionally, such as when normal maintenance is occurring.