ESPLXD-ET Controller
Connecting the 2-Wire Cable
b
b
NOTE:
If installing communications wiring for IQ Software and/
or ET Manager, do not install the communications cables in the
same conduit as the 2-Wire path wiring.
A
Strip away approximately 6 in (15,24 cm) of the cable’s outer
sheathing; then strip approximately 5/8 in (1,58 cm) of the
insulation away from the ends of the two inner wires. See Wire
Splices and Field Decoder Connections for more details on the
correct way to splice wire connections.
B
Locate (or remove) the large knockout on the bottom of the
controller cabinet. Attach a conduit fitting to the bottom of the
cabinet; then attach conduit to the fitting.
C
Feed the 2-Wire communications cable through the conduit and
into the controller cabinet.
2
3
D
Using a thin blade screwdriver, connect the two wire ends to a
set of large two-wire path terminals on the ESPLXD-ET decoder
module. When finished, tug gently on the wires to make sure the
connections are tight.
4
b
e
If you have multiple two wire paths then repeat this process to
connect those wire ends to the other LXD module terminals as
desired.
E
Once wiring is completed, fill top of conduit with waterproof
caulking to prevent insect intrusion into the controller cabinet.
5