SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
91
Table 3.9 Monitor Output
Terminal
Name (Default)
Function (Signal Level)
PO
Pulse train output
(Output frequency)
32 kHz (maximum)
Refer to
“
Pulse Train Output
”
on page
for more information.
AO1
Analog monitor output 1
(Output frequency)
Select voltage or current output.
•
0 V to 10 V/0% to 100%
•
-10 V to +10 V/-100% to +100%
•
4 mA to 20 mA (receiver recommended impedance: 250 Ω)
Note:
Select with jumper switch S5 and
H4-07 [AO1 Signal Level Select]
or
H4-08 [AO2 Signal Level Select]
.
AO2
Analog monitor output 2
(Output current)
A0V
Monitor common
0 V
■
External Power Supply Input Terminals
This chapter contains a list of the functions of the external power supply input terminals.
Table 3.10 External Power Supply Input Terminals
Terminal
Name (Default)
Function
E24V
External 24 V power supply input
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
A0V
External 24 V power supply ground
0 V
■
Serial Communication Terminals
This chapter contains a list of the functions of serial communication terminals and functions.
Table 3.11 Modbus Communication
Terminal
Terminal Name
Function (Signal Level)
RS485+
Communication input/output (+)
Modbus communications
Use an RS-485 cable to connect the drive.
Note:
Set DIP switch S2 to ON to enable the termination
resistor in the last drive in a Modbus network.
•
RS-485
•
Modbus communication protocol
•
Maximum 115.2 kbps
RS485-
Communication output (-)
A0V
Signal ground
0 V
◆
Control Circuit Terminal Configuration
A - Terminal block (TB2-3)
B - Terminal block (TB2-2)
C - Terminal block (TB2-1)
D - Terminal block (TB1)
E - Terminal block (TB3)
F - Terminal block (TB4)
Figure 3.34 Control Circuit Terminal Arrangement
Use the tables in this section to select the correct wires. Use shielded wire for the control circuit terminal block.
Use crimp ferrules on the wire ends to make wiring easier and more reliable.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...