568
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
■
b5-10 PID Output Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
b5-10
(01AE)
RUN
PID Output Gain Setting
Sets the amount of gain to apply to the PID output.
1.00
(0.00 - 25.00)
Applies a gain to the PID output and can help when
b5-01 = 1 [PID Enable = Enabled]
and
b5-72 = 0 [PID D-
FF Mode = D=Fdback]
.
■
b5-11 PID Output Reverse Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-11
(01AF)
PID Output Reverse
Selection
Sets the function that enables and disables reverse motor rotation for negative PID control output.
0
(0, 1)
This parameter is disabled when
b5-01 = 3, 4 [Disabled = Fref + PID Trim, Fref + PID Trim (D on feedback)]
.
There is no limit for PID output (PID output can be positive or negative). Operates the same as setting
“
1:
Negative lower limit
”
.
0 : 0 lower limit
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative lower limit
When the PID output is negative, the motor will rotate in reverse.
■
b5-12 Fdback Loss Select Mode
No.
(Hex.)
Name
Description
Default
(Range)
b5-12
(01B0)
Fdback Loss Select Mode
Sets the drive response to PID feedback loss. Sets drive operation after the drive detects PID
feedback loss.
0
(0 - 5)
0 : DO Only Always
The MFDO terminal set for
PID Feedback Low
or
PID Feedback High [H2-01 to H2-03 = 3E, 3F]
activates.
When the drive detects feedback loss, the keypad will not show an alarm and the drive will continue operation.
When the feedback signal is less than the level set in
b5-13 [Fdback Loss Lvl]
for longer than the time set in
b5-
14 [Fdback Loss Time]
, the MFDO terminal set for a
PID Feedback Low
activates.
When the feedback signal is more than the level set in
b5-36 [PID HiHi Limit Level]
for longer than the time set
in
b5-37 [PID HiHi Time]
the MFDO terminal set for a
PID Feedback High
activates.
When the feedback value is not in the detection range, the drive resets the fault output.
1 : AL+DO Always
The drive detects
FbL [PID Feedback Loss]
and
FbH [Excessive PID Feedback]
. The MFDO terminal set for
PID Feedback Low
or
PID Feedback High [H2-01 to H2-03 = 3E, 3F]
activates. The output terminal set for
Alarm [H2-01 to H2-03 = 4]
activates and the drive continues operation.
When the feedback signal is less than the level set in
b5-13
for longer than the time set in
b5-14
, the MFDO
terminal set for a
PID Feedback Low
activates.
When the feedback signal is more than the level set in
b5-36
for longer than the time set in
b5-37
, the MFDO
terminal set for a
PID Feedback High
activates.
When the feedback value is not in the detection range, the drive resets the fault output.
2 : FLT+DO Always
The drive detects
FbL
and
FbH
. The output terminal set for
Fault [H2-01 to H2-03 = 3]
activates and the motor
coasts to stop.
When the feedback signal is less than the level set in
b5-13
for the time set in
b5-14
, the drive detects
FbL
.
When the feedback signal is more than the level set in
b5-36
for the time set in
b5-37
, the drive detects
FbH
.
3 : DO Only@PID Enable
The MFDO terminal set for
PID Feedback Low
or
PID Feedback High
activates. When the drive detects feedback
loss, the keypad will not show an alarm and the drive will continue operation.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...