SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
585
Figure 12.38 Timing Diagram of Acceleration and Deceleration Times
■
Use Motor Selection to Switch Acceleration and Deceleration Times
When you set
H1-xx = 61 [MFDI Function Select = Motor 2 Select]
, you can activate and deactivate the input
terminal to switch between motor 1 and motor 2.
Note:
You cannot use the Motor 2 Selection function with PM motors.
shows the possible acceleration and deceleration time combinations when you use the Motor 2
Selection function.
Table 12.15 Motor Selection and Acceleration and Deceleration Times
H1-xx = 18
[Ac/Dec Time1]
H1-xx = 61 [Motor 2 Select]
Motor 2 Selection: OFF
Motor 2 Selection: ON
Acceleration Time
Deceleration Time
Acceleration Time
Deceleration Time
OFF
C1-01
C1-02
C1-05
C1-06
ON
C1-03
C1-04
C1-07
C1-08
■
Use Output Frequency Level to Switch Acceleration and Deceleration Times
The drive can use output frequency to automatically switch between different acceleration and deceleration times.
The acceleration and deceleration times for the drive are switched automatically. When the output frequency =
C1-11 [Ac/Dec Switch Frequency]
, the drive automatically switches the acceleration and deceleration times. Set
C1-11 = 0.0 Hz
to disable this function.
Note:
•
Acceleration and deceleration times set to MFDIs are more important than the automatic switch using the frequency level set in
C1-11
.
For example, if the MFDI set for
Ac/Dec Time1 [H1-xx = 18]
is activated, the drive will use only accel/decel time 2 (or accel/decel
time 4 for motor 2). If you use a frequency level set in
C1-11
, the drive will not automatically switch acceleration and deceleration
times.
•
If Motor 2 Selection
[H1-xx = 61]
is activated, the drive will set the acceleration/deceleration time to
C1-05
and
C1-06
for motor 2
when the output frequency is more than the frequency level set in
C1-11
.
Figure 12.39 Accel/Decel Time Switchover Freq
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...