SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
767
Figure 12.123 Cancel KEB Operation without Using the KEB Ride-Thru if Restoration of Power Occurs while the
Control Power (Power Supply to the Control Board) is Maintained
*1
When setting
L2-07 = 0.00
, the drive reaccelerates in accordance with the valid
Acceleration Time [C1-01,
C1-03, C1-05, C1-07]
, and normal operation resumes.
Use the KEB Ride-Thru to Cancel KEB Operation when Restoration of Power Occurs while the Control
Power (Power Supply to the Control Board) is Maintained
shows an example with this configuration:
•
L2-01 = 4
.
•
Use
KEB Ride-Thru 1 [H1-xx = 40, 41]
or
KEB Ride-Thru 2 [H1-xx = 42, 43]
.
The drive starts deceleration through KEB operation. When the motor decelerates for the time set in
L2-10
, the
drive measures the DC bus voltage and the status of the digital input set for KEB Ride-Thru. When the DC bus
voltage is less than the level set in
L2-11
, or if the digital input set to KEB Ride-Thru is active, deceleration
continues. When the voltage level is more than the value set to
L2-11
, usual operation continues. The drive
accelerates the motor to the frequency reference value before the power loss, and usual operation continues. When
the KEB Ride-Thru continues to be input after the time set in
L2-02
is expired, the drive uses the KEB Ride-Thru
function to continue to decelerate. When you cancel the KEB Ride-Thru, the motor accelerates again, and usual
operation continues.
Figure 12.124 Use the KEB Ride-Thru to Cancel KEB Operation when Restoration of Power Occurs while the Control
Power (Power Supply to the Control Board) is Maintained
*1
When
L2-07 = 0.00
, the drive accelerates again as specified by the applicable
Acceleration Time [C1-01, C1-
03, C1-05, C1-07]
, and usual operation continues.
KEB Operation when L2-01 = 5 [Kinetic Energy Backup: DecelStop]
The drive starts deceleration through KEB operation. The drive will continue to decelerate until the motor comes
to the minimum output frequency or a complete stop. If you return power during deceleration, the drive continues
to decelerate. If you do not input the Run command, the motor cannot restart.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...