SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
799
Note:
•
If
A1-02 = 4
and you do not do Rotational Auto-Tuning, control will not be stable. This can cause
CF
faults when you ramp to stop. If
the drive detects
CF
, do Rotational Auto-Tuning and Line-to-Line Resistance Tuning.
•
If you input a Stop command while the motor rotates on the load side and
A1-02 = 4
to use torque control, load conditions can cause
operation to not stop and can also cause
CF
faults. Make sure that you do Rotational Auto-Tuning and Line-to-Line Resistance Tuning
correctly and then set
L8-20 = 0
.
■
L8-27 OverCurr Det Gain
No.
(Hex.)
Name
Description
Default
(Range)
L8-27
(04DD)
OverCurr Det Gain
Sets the PM motor overcurrent detection level as a percentage of the motor rated current value.
300.0%
(0.0 - 400.0%)
If the drive rated current is much higher than the motor rated current, PM motor magnets can demagnetize when
current flows at the drive overcurrent detection level. When the overcurrent detection level is low, adjust this
parameter to prevent motor demagnetization.
If you set
L7: TORQUE LIMIT
and
L8-27
to the same value or almost the same value, the drive can detect
oC
[Overcurrent]
. Lower the torque limit when you use a Yaskawa motor. When you use a non-Yaskawa motor,
measure the irreversible demagnetization resistance before you adjust this parameter.
Note:
The overcurrent detection function detects the lower of these two values:
•
Drive overcurrent level
•
Motor rated current ×
L8-27
/ 100
■
L8-29 LF2 Unbalance Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-29
(04DF)
LF2 Unbalance Selection
Sets the function to detect
LF2
.
1
(0, 1)
This function prevents damage to PM motors. Current unbalance can heat a PM motor and demagnetize the
magnets. When the current is unbalanced, the drive will detect
LF2
to stop the motor and prevent damage to the
motor.
0 : Disabled
1 : Enabled
■
L8-31 LF2 Detect Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-31
(04E1)
LF2 Detect Time
Sets the LF2 [Output Current Imbalance] detection time.
3
(1 to 100)
When the output current is unbalanced for longer than the time set in
L8-31
, the drive detects
LF2
.
Note:
•
Set
L8-29 = 1 [LF2 Unbalance Selection = Enabled]
to enable this parameter.
•
If the drive detects
LF2
by error, increase the setting value of
L8-31
in 5-unit increments.
•
The keypad shows this parameter when
E9-01 = 1 [Motor Type Selection = PM]
under EZ Open Loop Vector Control.
■
L8-32 Fan Failure Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-32
(04E2)
Fan Failure Selection
Sets operation when the drive detects
FAn [Internal Agitating Fan Fault]
.
1
(0 - 4)
0 : Ramp->Stop
The drive ramps to stop in the selected deceleration time. Fault relay output terminal 1NO-1CM will activate, and
1NC-1CM will deactivate.
1 : Coast->Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal 1NO-1CM will activate, and
1NC-1CM will deactivate.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...