SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
201
Table 5.10 Recommended Wiring Tools
Screw
Adapter
Bit
Torque Driver Model
(Tightening Torque)
Torque Wrench
Model
Manufacturer
M4
Bit
SF-BIT-SL 1,0X4,0-70
PHOENIX CONTACT
TSD-M 3NM
(1.2 - 3 N∙m)
-
M5
Bit
SF-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
Wire Gauge ≤ 25 mm
2
(AWG 10):
TSD-M 3NM
(1.2 - 3 N∙m)
Wire Gauge ≤ 25 mm
2
(AWG 10):
-
Wire Gauge ≥ 30 mm
2
(AWG 8):
-
Wire Gauge ≥ 30 mm
2
(AWG 8):
4.1 - 4.5 N∙m
M6
Bit
SF-BIT-HEX 5-50
PHOENIX CONTACT
-
5 - 9 N∙m
M6
Bit
SF-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
-
3 - 3.5 N∙m
M8
Bit
SF-BIT-HEX 6-50
PHOENIX CONTACT
-
8 - 12 N∙m
M10
Bit
SF-BIT-HEX 8-50
PHOENIX CONTACT
-
12 - 14 N∙m
*1
When wiring drive models 2056 and 4089 and smaller, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.
■
Wire Gauges and Tightening Torques as Specified by UL Standards
Comply with local standards for correct wire gauges in the region where the drive is used.
WARNING!
Electrical Shock Hazard. Only connect peripheral options, for example a DC reactor or braking resistor, to terminals
+1, +2, +3, -, B1, and B2. Failure to obey can cause death or serious injury.
Refer to
Notes on Wire Gauges and Tightening Torques on page 77
for general conditions
Drives from model 2257 and from model 4208, use UL-approved closed-loop crimp terminals on the drive main
circuit terminals. Use the tools recommend by the terminal manufacturer and make sure that the terminals are
correctly connected.
Select the correct wires for main circuit wiring.
Three-Phase 200 V Class
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable
Gauge
AWG, kcmil
(mm
2
)
Wire Stripping
Length
mm
Terminal Screw
Size and Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
2004
R/L1, S/L2, T/L3
14
14 - 6
(2.5 - 16)
14 - 6
(2.5 - 16)
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
14
14 - 6
(2.5 - 16)
14 - 6
(2.5 - 16)
10
M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2
14
14 - 3
(2.5 - 25)
14 - 3
(2.5 - 25)
18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2
14
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.5 - 15)
10
14 - 8
(2.5 - 10)
-
-
M4
1.2 - 1.5
(10.6 - 13.3)
2006
R/L1, S/L2, T/L3
14
14 - 6
(2.5 - 16)
14 - 6
(2.5 - 16)
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
14
14 - 6
(2.5 - 16)
14 - 6
(2.5 - 16)
10
M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2
14
14 - 3
(2.5 - 25)
14 - 3
(2.5 - 25)
18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2
14
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.5 - 15)
10
14 - 8
(2.5 - 10)
-
-
M4
1.2 - 1.5
(10.6 - 13.3)
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...