SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
703
Note:
•
When you use 2 motors, the drive applies the protective function set in
L1-01 [Motor Cool Type for OL1 Calc]
to motor 1 and motor 2.
•
You cannot switch between motors 1 and 2 during run. If you try to switch motors when they are running, it will cause a
rUn
error.
•
After you switch between encoder motors, you must wait 500 ms minimum to input a Run command. You must wait 200 ms minimum
for other control methods.
■
60: Timer Fn Input
Setting
Function
Description
60
Timer Fn Input
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 39]
.
Note:
Refer to
“
b4: TIMER
”
for more information.
■
62: Up Command
Setting
Function
Description
62
Up Command
Sets the command to use a button to increase the drive frequency reference. You must also set Setting 63
[Down Command]
.
ON : Raises the frequency reference.
OFF : Holds the current frequency reference.
Note:
•
If you only set the Up command or only set the Down command, the drive will detect
oPE03 [Multi-Function Input Setting Err]
.
•
If you set two or more of these functions at the same time,
oPE03
occurs:
–
Up/Down command
–
Accel/Decel Ramp Hold
–
Reference sample hold
–
Offset Frequency 1, 2, 3 addition
–
Up/Down 2 Command
•
You can use the Up/Down command when the keypad is in REMOTE mode and when
b1-01 ≠ 0 [Freq. Ref. Sel. 1 ≠ Keypad]
.
•
The Up/Down command does not function when you use
Ext Ref 1/2 [H1-xx = 9]
to switch to parameter
b1-15 [Freq. Ref. Sel. 2]
.
When you input the Up command, the frequency reference increases. When you input the Down command, the
frequency reference decreases.
The Up and Down commands are more important than all other frequency references. When the Up/Down
command is enabled, the drive will ignore these frequency references:
•
Frequency reference from Keypad
[b1-01 = 0]
•
Frequency reference from Analog Input
[b1-01 = 1]
•
Frequency reference from Pulse Train Input
[b1-01 = 4]
shows the Up and Down commands with their operation.
Table 12.42 Up Command and Down Command
Command status
Drive operation
Up command (62)
Down command (63)
OFF
OFF
Keeps the current frequency reference.
ON
OFF
Increases the frequency reference.
OFF
ON
Decreases the frequency reference.
ON
ON
Keeps the current frequency reference.
Combine Frequency Reference Hold Functions and Up/Down Commands
•
When you clear the Run command or when d4-01 = 0 [FRef Hold Selection = Disabled] and you restart the
drive, the Up/Down command resets to 0.
•
When
d4-01 = 1 [Enabled]
, the drive saves the frequency reference set during the Up/Down command. When
you cycle the Run command or restart the drive, the drive saves the frequency reference value and restarts the
motor at this frequency value. After you clear the Run command, activate the terminal set for the Up command
or Down command to set the saved reference value to 0.
Note:
Refer to
“
d4-01 FRef Hold Selection on page 616
”
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...