SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
551
Parameter
Current Detection 2
Speed Estimation
b3-55 [Speed Curr Rise Time]
-
-
b3-56 [Inv Rot Srch Time]
-
×
Note:
•
To use Speed Estimation Speed Search with V/f Control, do Rotational Auto-Tuning before you set the Speed Search function. If the
wire length between the drive and motor changed since the last time you did Auto-Tuning, do Stationary Auto-Tuning for Line-to-Line
Resistance process again.
•
If
A1-02 = 5, 6 [PM OLVector, PM AOLVector]
and the wiring distance between the motor and drive is long or if the motor is coasting
at more than or equal to 200 Hz, do not use Speed Search to restart the motor. Use Short Circuit Braking.
■
Current Detection 2
Use this Speed Search function with induction motors. Set
b3-24 = 2 [SpSrch Method Selection = Current Det2]
.
Current Detection Speed Search injects current into the motor to detect the speed of an induction motor. Speed
Search increases the output voltage for the time set in
L2-04 [Powloss Ramp Time@recovery]
, starting from the
maximum output frequency or the frequency reference.
Figure 12.22 Current Detection Speed Search after Momentary Power Loss
Note:
After you return power, the drive will not do Speed Search until the time set in
b3-05 [SpSrch Delay Time]
is expired. Thus, the drive
will not always start Speed Search although the time set in
L2-03 [Min Baseblck Time]
is expired.
If you enter the Run command at the same time as Speed Search, the drive will not do Speed Search until the time
set in
L2-03
is expired. If the value set in
L2-03
<
b3-05
, the drive will use the wait time set in
b3-05
.
Figure 12.23 Speed Search Selection at Start (Current Detection Type)
WARNING!
Sudden Movement Hazard. If you do Current Detection Speed Search with light loads or a stopped motor, the
motor can suddenly accelerate and cause serious injury or death.
Note:
•
You cannot use Current Detection Speed Search with PM motors.
•
If the motor is rotating in reverse, you cannot do Speed Search.
•
If the drive detects
oL1 [Motor Overload]
during Current Detection Speed Search, decrease the value set in
b3-03
.
•
If the drive detects
oC [Overcurrent]
or
ov [Overvoltage]
during Current Detection Speed Search after the drive recovers from a
momentary power loss, increase the value set in
L2-03
.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...