
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
33
2.2
Installation Environment
The installation environment is important for the lifespan of the product and to make sure that the drive
performance is correct. Make sure that the installation environment agrees with these specifications.
Environment
Conditions
Area of Use
Indoors
Power Supply
Overvoltage Category III
Ambient Temperature
Setting
Open chassis type (IP20): -10 °C to +60 °C (14 °F to 140 °F). Derate the output current and output voltage if the drive is installed in areas with
ambient temperatures from +50 °C to +60 °C (122 °F to 140 °F).
Enclosed wall-mounted type (UL Type 1): -10 °C to +40 °C (14 °F to 104 °F)
•
Drive reliability is better in environments that do not have wide temperature fluctuations.
•
When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
•
Oil mist, corrosive or flammable gas, or dust
•
Metal powder, oil, water, or other unwanted materials
•
Radioactive materials or flammable materials, including wood
•
Harmful gas or fluids
•
Salt
•
Direct sunlight
Keep wood and other flammable materials away from the drive.
Altitude
1000 m (3281 ft.) maximum
Note:
Derate the output current by 1% for each 100 m (328 ft.) to install the drive in altitudes between 1000 m to 4000 m (3281 ft. to 13123 ft.).
It is not necessary to derate the rated voltage in these conditions:
•
Installing the drive at 2000 m (6562 ft.) or lower
•
Installing the drive between 2000 m to 4000 m (6562 ft. to 13123 ft.) and grounding the neutral point on the power supply.
Contact the manufacturer or your nearest sales representative when not grounding the neutral point.
Vibration
•
10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
•
20 Hz to 55 Hz:
Models 2004 to 2211, 4002 to 4168: 0.6 G (5.9 m/s
2
, 19.36 ft/s
2
)
Models 2257 to 2415, 4208 to 4675: 0.2 G (2.0 m/s
2
, 6.56 ft/s
2
)
Installation Position
Install the drive vertically for sufficient cooling airflow.
NOTICE:
Do not put drive peripheral devices, transformers, or other electronics near the drive. Shield the drive from electrical
interference if components must be near the drive. Failure to obey can cause incorrect operation.
NOTICE:
Do not let unwanted objects, for example metal shavings or wire clippings, fall into the drive during drive installation
and project construction. Put a temporary cover over the top of the drive during installation. Remove the temporary cover before
start-up or the drive will overheat. Failure to obey can cause damage to the drive.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...