SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
709
Note:
Refer to Modbus communications
“
Self-Diagnostics
”
for the self-diagnostics procedure.
■
90 to 99: Q2pack DI1 to 10
Setting
Function
Description
90 to 99
Q2pack DI1 to 10
Sets digital inputs used with Q2pack. Refer to the Q2pack Online Manual for more information.
Note:
You cannot set values 90 to 99 for inverse output.
■
9F: Q2pack Disable
Setting
Function
Description
9F
Q2pack Disable
Sets operation of the Q2pack program saved in the drive.
Note:
Set
A1-07 = 2 [Q2pack Enable = With DI]
to use this function.
ON : Disabled
OFF : Enabled
■
101 to 19F: Inverse Input of 1 to 9F
Setting Value
Function
Description
101 to 19F
Inverse Input of 1 to 9F
Sets the function of the selected MFDI to operate inversely. To select the function, enter
“
1xx
”
, where the
“
xx
”
is the function
setting value.
For example, to use the inverse input of
46 [ASR I Reset]
, set
H1-xx = 146
.
Note:
You cannot use inverse input for all functions. Refer to
for more information.
◆
H2: DIGITAL OUTPUTS
■
Multi-Function Digital Outputs
H2 parameters
set the MFDO terminal functions.
H2-01 Multi-Function Digital Output 1, H2-02 Multi-Function Digital Output 2, H2-03 Multi-Function Digital
Output 3
The drive has three MFDO terminals.
shows the default function settings for the terminals.
Table 12.44 MFDO Terminals Default Function Settings
No.
Name
Default Setting
Function
H2-01
Multi-Function Digital Output 1
5
@Run
H2-02
Multi-Function Digital Output 2
7
Zero Speed
H2-03
Multi-Function Digital Output 3
F
SpeedAgree1
Refer to
to set
H2-xx [DO Function Select]
.
Table 12.45 MFDO Setting Value
Setting Value
Function
0
Through Mode
1
Drive Ready
2
Drive Enable
3
Fault
4
Alarm
5
@Run
6
@Reverse
7
Zero Speed
Setting Value
Function
8
ZeroServo ok
9
@Regeneration
A
@SpeedLimit
B
@FreqOutput
C
@Standby
D
LO/RE Status
E
EDM Safety
F
SpeedAgree1
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...